background image

 

AT500-0200-1b (10-2010)  DCN0528                                                                                                                       7 

3. 

TROUBLESHOOTING INFORMATION 

3.1 

Proper Power-Up

 

Use a mA meter to measure the output current (see section 2.2 for mA monitor connections). When power is applied, the output 
should go to 4.00 mA for at least 1 second, and then to either the measured level or an alarm condition output. If this does not 
happen, the transmitter may not be receiving enough power, or the main electronic is defective.  Excessive current above 21 mA 
is also an indication of improper power-up or defective electronics. 
 

 

 

Valid Current Loop Outputs: 

 

-21.0 mA 

If HI ALARM was selected, a loss of signal, no float detected, problem with the configuration, or a malfunction, 

will cause the output to be set to the alarm condition of 21.0 mA. 
 

 

20.6 mA 

OVERRANGE: When the level increases above the 20 mA point, the output will continue up to 20.6 mA and 

then latch at that value, until the level comes back down again. 

 

 

3.8 mA - 20.6 mA

 Normal output range

 

 

 

3.8 mA

 UNDERRANGE: When the level increases below the 4 mA point, the output will continue down to 3.8 mA and 

then latch at that value, until the level comes back up again.

 

 

 

-

3.6 mA

 If LOW ALARM was selected, a loss of signal, no float detected, problem with the configuration, or a malfunc-

tion, will cause the output to be set to the alarm condition of 3.6 mA. 

 

3.2 

Output Stability

 

If the current output occasionally jumps up or down but not to an alarm condition:  
 
This can be an indication of noise or grounding problem.  Field wiring should be run with an individually shielded cable.  Insure 
that the transmitter housing is effectively connected to earth ground. 
 
There may be a location on the tube that has retained some magnetization, and needs to be cleared. This can happen if a mag-
net or float was used to manually calibrate the sensor and if it was pulled away at 90 degrees from the tube.  To avoid this, al-
ways slide the magnet parallel to the tube and remove it by going past either end of the tube. To clear any remaining magnetiza-
tion, slide a magnet or float against and parallel to the tube, from one end to the other.

  

 

3.3 

Conversion from AT500 to AT600 or AT600 to AT500 

 

It is possible to convert a bottom connected AT600 to an AT500 by adding a float and other parts.  It is also possible to convert an 
AT500 to a bottom connected AT600 by adding mounting clips.  Please consult the factory.   
 
It is not possible to convert a top connected AT600 to an AT500 or vice versa.  If you wish to make this change, the transmitters 
will have to be replaced. 

Summary of Contents for K-TEK AccuTrak AT500

Page 1: ...AT500 0200 1b 10 2010 DCN0528 ...

Page 2: ...tting 4 2 4 1 Setting ALARM to 3 6 mA Low Alarm 5 2 4 2 Setting ALARM to 21 mA High Alarm 5 2 5 4 mA 20 mA DAC Trim 5 2 5 1 Setting 4 0 mA DAC Trim 5 2 5 2 Setting 20 0 mA DAC Trim 5 3 TROUBLESHOOTING INFORMATION 7 3 1 Proper Powerup 7 3 2 Output Stability 7 3 3 Conversion from AT500 to AT600 or AT600 to AT500 7 4 APPENDIX A 8 4 1 Installation Drawings 8 5 APPENDIX B 10 5 1 FMEDA Certificate 10 6 ...

Page 3: ...ff of the magnet assembly within the float riding on the sensor tube 2 INSTALLATION AND STARTUP WARNING When fitted with a compression fitting the sensor tube is shipped with a set of TEFLON ferrules and a set of STAINLESS STEEL ferrules in a separate bag The TEFLON ferrules are only in tended for low pressure applications for higher operating pressures and or permanent installation replace the TE...

Page 4: ...d 2 3 Reversing Action If required transmitter output can be reversed by following these steps Note this reverses the 4 20 mA output Bring the level to 50 or 10 Enter the calibration mode by placing Magnet at position X for 2 seconds Slide magnet from position X to position Z to temporarily set the ZERO 4 00mA setpoint this step is verified by checking that the output is now at 4 00 mA Bring the l...

Page 5: ...equired the unit s 4 ma and 20 ma outputs can be trimmed as follows 2 5 1 Setting 4 0 mA DAC Trim Enter the 4 mA DAC TRIM MODE by applying power to the unit while Magnet is at position Z Magnet at position Z will decrease the output at 0 01 mA intervals Moving the magnet to position S will increase the output at 0 01 mA intervals Continue to Increase Decrease the output until the output is at 4 00...

Page 6: ...NT DAC 01 mA SW Z DECREMENT DAC 01 mA POWER UP SW Z ENTER 4 0 mA DAC TRIM MODE SW S INCREMENT DAC 01 mA SW Z DECREMENT DAC 01 mA POWER UP SW X ENTER ALARM MODE SETUP SW S SET 21 mA ALARM SW Z SET 3 6 mA ALARM POWER UP SW X 2 sec ENTER CALIBRATION MODE SW S SET 20 mA 100 POINT SW Z SET 4 mA 0 POINT NORMAL OPERATION Magnetic switchpoints are located on lines S X Z at points 90 degrees from the condu...

Page 7: ...ted a loss of signal no float detected problem with the configuration or a malfunc tion will cause the output to be set to the alarm condition of 3 6 mA 3 2 Output Stability If the current output occasionally jumps up or down but not to an alarm condition This can be an indication of noise or grounding problem Field wiring should be run with an individually shielded cable Insure that the transmitt...

Page 8: ...AT500 0200 1b 10 2010 DCN0528 8 4 APPENDIX A 4 1 Installation Drawings ...

Page 9: ...AT500 0200 1b 10 2010 DCN0528 9 4 1 Installation Drawings continued ...

Page 10: ...AT500 0200 1b 10 2010 DCN0528 10 5 APPENDIX B 5 1 ...

Page 11: ...er alterations misuse abuse improper or inadequate adjustments applications or servicing of the product K TEK s warranty does not include onsite repair or services Field service rates can be supplied on request If a product is believed to be defective the original purchaser shall notify K TEK and request a Returned Material Authorization before returning the material to K TEK with transportation p...

Page 12: ...AT500 0200 1b 10 2010 DCN0528 12 6 2 RMA Form ...

Page 13: ...AT500 0200 1b 10 2010 DCN0528 13 6 3 EU Declaration of Conformity ...

Page 14: ...AT500 0200 1b 10 2010 DCN0528 14 ...

Reviews: