![ABB ISL-A 24 Instruction Manual Download Page 4](http://html2.mh-extra.com/html/abb/isl-a-24/isl-a-24_instruction-manual_5043126004.webp)
2024-01-24
4/4
—
TECHNICAL FEATURES
Auxiliary voltage supply
24-48V 50-60Hz/d.c. ± 20%
Maximum consumption
3 VA-3W
Measure current
max 0,5 mA
Internal impedance
50 kΩ
Threshold tripping
Settable 10 ÷ 60 k
Ω
(5 levels with micro-switches)
Tripping delay
About 0.2 seconds
Signalling and button
led ON, led TRIP, led +, led -
Output
Relay changeover contact NO-C-NC max 250V 5A
Working and storing temperature
-10 ÷ 60°C / -20 ÷ 70°C
Relative humidity
≤ 95 %
Insulation test
2,5 kV 60 sec. / 4 kV imp. 1,2/50μs
Mounting position
Any
Wiring type
Screw terminals / cross section cables 4 mm²
Protection degree
Front with cover: IP 40
–
Enclosure: IP 20
Mounting according DIN 50022
Snap on DIN rail 35mm / 3 modules 17,5 mm
Weight
About 300 g
Standards
Safety EN 61010-1
Electromagnetic compatibility IEC-EN 61326-1
For application not described in this manual it’s better to see specific document or to contact the technical
service.
—
NOTE
At reason of the evolution of standards and products, the company reserves to modify in every time the features of the product described
in this document, that it’s necessary to verify preventively.
The liability of the producer for damage caused by defect of the product ”can be reduced or deleted (…) when the damage is ca
used joint
by a defect of product or for blame of the damaged or a person of which the damaged is responsible” (Article 8, 85/374/C
EE).
Snap on DIN rail 35mm
(DIN 50022)
3 modules 17,5 mm
1
DIMENSIONS