ABB ISL-A 24 Instruction Manual Download Page 4

 

 

2024-01-24

 

 

4/4

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

TECHNICAL FEATURES

 

Auxiliary voltage supply 

24-48V 50-60Hz/d.c. ± 20% 

Maximum consumption 

3 VA-3W 

Measure current 

max 0,5 mA 

Internal impedance 

50 kΩ

 

Threshold tripping 

Settable 10 ÷ 60 k

Ω

 (5 levels with micro-switches) 

Tripping delay 

About 0.2 seconds 

Signalling and button 

led ON, led TRIP, led +, led - 

Output 

Relay changeover contact NO-C-NC max 250V 5A 

Working and storing temperature 

 -10 ÷ 60°C / -20 ÷ 70°C 

Relative humidity 

≤ 95 %

 

Insulation test 

2,5 kV 60 sec. / 4 kV imp. 1,2/50μs

 

Mounting position 

Any 

Wiring type 

Screw terminals / cross section cables 4 mm² 

Protection degree 

Front with cover: IP 40 

 Enclosure: IP 20 

Mounting according DIN 50022 

Snap on DIN rail 35mm / 3 modules 17,5 mm 

Weight 

About 300 g 

Standards 

Safety EN 61010-1 

Electromagnetic compatibility IEC-EN 61326-1 

 

For application not described in this manual it’s better to see specific document or to contact the technical 

service. 

 

NOTE 

At reason of the evolution of standards and products, the company reserves to modify in every time the features of the product described 

in this document, that it’s necessary to verify preventively.

 

The liability of the producer for damage caused by defect of the product ”can be reduced or deleted (…) when the damage is ca

used joint 

by a defect of product or for blame of the damaged or a person of which the damaged is responsible” (Article 8, 85/374/C

EE). 

 

 

 

Snap on DIN rail 35mm 

(DIN 50022) 

3 modules 17,5 mm 

 

1

 

DIMENSIONS

 

Reviews: