INSTRUCTION MANUAL

 

ISL-A 24/ ISL-A 48

 

DEVICE FOR INSULATION PERMANENT CONTROL FOR ISOLATED NETWORKS (IT)

 

 

GENERAL

 

In IT electrical distribution networks with isolated neutral, the high insulation impedance prevents earth faults 
from generating currents that would dangerously elevate the potential of exposed conductive parts. 

Therefore, in case of earth leakage in an IT network, it is not necessary to interrupt the supply, but it is still 
essential to continually monitor the insulation level in order to detect faults and restore optimal functioning 
of the system. 

The ISL-C 230 is an Insulation Monitoring Device for IT networks with voltages of 24 to 48 V ac/dc. These de-
vices measure the potential variation of two polarities in reference to earth, to signal when the insulation is 
decreasing below a fixed value. 

Auxiliary supply is taken from the under-control network. On the front panel, there is signaling for the device 
being ON, TEST and RESET push-buttons, and three LEDs for signaling a tripping (TRIP) and to indicate the 
polarity of the line under control that has low insulation. 

The threshold for trip is regulated by a series of micro-switches. There is a changeover contact relay available 
to transfer the information of the low insulation signaling to a remote panel. 

 

INSTALLATION

 

The installation must be carried out by qualified and authorized personnel and in the absence of voltage.  
Make sure that the instrument is O.K. and has not been damaged during transport.  
Make sure that the voltage supply is compatible with the operating voltage of the instrument.   
For each independent line, it's possible to use only one control device.  
The device is a 3 modules (17.5mm) DIN version with snap on 35mm DIN rail.  
It has a sealable transparent front protection cover.  
The green LED ON will light up after the connections are set and the instrument is powered on. 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

 

1.

 

Green LED ON, signaling the instrument is working. 

2.

 

Red LED TRIP, signaling a trip for low insulation; in manual reset 

mode, it is necessary to press the RESET to cancel the signaling. 

3.

 

Red LED TRIP (+ / -), in low insulation status, signals the polarity 

under the trip threshold in a direct line, while both LEDs will be on in 

an alternating line, functioning in automatic reset. 

4.

 

TEST button to test the instrument's functionality. 

5.

 

RESET button to cancel the trip signaling (manual reset). 

6.

 

Micro-switches to select the threshold for trip. 