ABB IR/KB Technical Data Download Page 2

Installation location

The recommended mounting height is 2.3 m. The unit can be 

mounted between 2.1 m and 2.5 m without adjustment, when 

mounted on a vertical surface. 

It may only be mounted on permanent, vibration-free walls. 

Large objects situated before the detector obstruct the 

detection range. The detector may not be subject to direct 

sunlight, heat sources and strong draughts (e.g. fans of 

air-conditioning systems) to prevent false alarms. 

Preparation and mounting

The screw must be loosened (do not unscrew fully) to 

remove the cover. Then insert a flat screwdriver into the slot 

underneath the screw and twist it. When the detector is 

opened, the electronic circuit board can be unlatched via the 

two catches and removed simultaneously from the plug-in 

socket. On the lower housing section, the selected cable 

entry points and mounting apertures can be knocked out. 

Introduce the cables, connect them and provide strain relief 

using the enclosed cable ties.

Wiring

The electronics are reinstalled after mounting the lower 

section. 

Caution:

 During all work, the light-sensitive sensor may not 

be touched. To refit the cover, engage the upper half using 

the two lugs and push both halves together (there will be an 

audible click), then tighten the screws.

Connect the detector as follows:

Infra-Red Motion Detector IR/KB

Infra-red section sensing range

Passive infra-red detector

Mounting location detection range

A = knockout for corner mounting
B = knockout for wall mounting
C = knockout for mounting with bracket
       

A

A

B

C

Opening the detector

L240

V+   V- MG¹ MG¹ MG² MG²  22³

Panel

L108

V+   V- MG¹ MG¹ 35    36  

L840/MG4 

 1    2    MG¹ MG¹ MG² MG²  13

MTS 4.12.1

11   12   MG¹ MG¹ MG² MG²   10

¹ Circuit – “Circuit for INTERNAL setting can be switched off (Cct 1-3)”
² Circuit – “Tamper”
³ Switch V+ via relay “Walk test” (24)

First or 

second last Infra-Red 

Detector 

IR/KB

 

Last or 

individual Infra-Red 

Detector 

IR/KB

 

Intrusion Alarm 

Panel

e.g . L240

V+

V-

MG1

MG2

C

22

23
24

MG9

MG10

C

Program relay 2 as "Walk test"

2.

7kΩ

2.

7kΩ

Summary of Contents for IR/KB

Page 1: ...eves its high level of immunity to false alarms by the use of high quality HEX technology with 12 fold pyro element detection in every zone and through pulse counting Technical data Voltage 12 V 9 V 16 V DC Current IR KB Quiescent 8 mA Alarm without LED 10 mA Alarm with LED 11 mA Alarm and tampering Break contact NC Contact load capacity 24 V DC 50 mA Test input Plus potential for LED activation E...

Page 2: ... the cables connect them and provide strain relief using the enclosed cable ties Wiring The electronics are reinstalled after mounting the lower section Caution During all work the light sensitive sensor may not be touched To refit the cover engage the upper half using the two lugs and push both halves together there will be an audible click then tighten the screws Connect the detector as follows ...

Page 3: ...t to ON with SW1 The red LED flashes to indicate detection of a slight movement If the red LED lights for 3 seconds this indicates detection of movement of a person within the detection range This message must cause a Circuit fault for this detector circuit when the detector zone is wired After connection of terminal 7 in accordance with the description and the VdS settings of the DIP switch the o...

Page 4: ...ior notice With regard to purchase orders the agreed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts ...

Reviews: