90
…4
CONFIGURATION
Without Adjustment
(Span Adjust = 1, Offset Adjust = 0)
With Adjustment
(typical example)
Engineering
Low
Engineering
High
Unadjusted Value
Engineering
Low
Engineering
High
Adjusted Value
Adjusted Value
Engineering
Low
Engineering
High
Engineering
Low
Engineering
High
Unadjusted Value
Offset Adjust (>0)
Span Adjust (<1)
…4.7.1
Analog Inputs
Offset adjust / Span adjust
Manually fine-tune the offset adjust and span adjust values to
remove process errors. These are calculated values applied
to the raw input signal.
Note.
If simulating thermocouple inputs, connect the
millivolt source using appropriate compensating cable – see
Section 5.4.2. For 2-lead resistance thermometers, either
connect the resistance box at the sensor end of the leads or
add the lead resistance to the calibration values.