Parameters
Note about navigation in the PDF: Key combination
Product Manual | EN | MG/S 11.100.1.1 | 9AKK108467A5941 Rev. B 31
'Alt + left arrow' jumps to the previous view/page
7.2.1.1
Read On Init Delay
This parameter is used to define the sending delay of the GroupValueRead telegram for Group Objects
with an initialization flag "I".
Note
I flag:
If the device is reset, a new GroupValueRead telegram is sent after the device restarts. The purpose of
this is to call the object value via a GroupValueResponse. Reasons for a device reset are a power failure
and subsequent bus voltage recovery, an explicit device reset, or an ETS download.
Explanation on knx.org ->
Option
0…255 s
Prerequisites for visibility
•
This parameter is in the
General
parameter window.
7.2.1.2
Time Telegram Rate
This parameter is used to define the waiting time between two telegrams before they are sent on the bus
(ABB i-bus
®
KNX). The bus load generated by the device can be limited using the
Time Telegram Rate
parameter. This limit relates to all telegrams sent by the device.
Option
0…5000 ms
Prerequisites for visibility
•
This parameter is in the
General
parameter window.