DGN/S 1.16.1

DGN/S 1.16.1

ABB i-bus

®

 KNX

DALI Gateway, Emergency Lighting, MDRC
DGN/S 1.16.1, 2CDG 110 142 R0011

Page 2 of 4

DGNS_1161_TD_EN_V1-0

2CDC 507 115 D0201

8

8

Operating and display elements

button 

 

button/LED 

 

LED  , green

LED  , yellow

DALI output test

for assignment of the physical address  

display for operation readiness

for displaying DALI fault, constant light 
for displaying test mode, slow flashing 
for displaying initialisation or more than 
64 DALI devices, quick flashing

Enclosure

IP 20

to EN 60529

Safety class

II

to EN 61140

Isolation category

overvoltage category

pollution degree

III to EN 60 664-1 

2 to EN 60664-1

KNX safety extra low voltage

SELV 24 V DC

DALI voltage

typical 16 V DC (9.5…22.5 V DC)

no-load voltage
  lowest supply current at 11.5 V
  highest supply current

to EN 60929 and EN 62386

16 V DC 
160 mA 
230 mA

Temperature range

operation

storage

transport

  -5 °C…+45 °C

-25 °C…+55 °C

-25 °C…+70 °C

Environmental conditions

humidity

maximum 93 %, moisture condensation 
should be excluded

Design

modular installation device (MDRC)

dimensions

mounting width

mounting depth

modular installation device, Pro 

M

90 x 72 x 64.5 mm (H x W x D)

4 modules at 18 mm

68 mm

Installation

on 35 mm mounting rail

to EN 60 715

Mounting position

as required

Weight

0.16 kg

Housing, colour

plastic housing, grey

Approvals

KNX to EN 50 090-1, -2

certification

CE mark

in accordance with the EMC guideline and 
low voltage guideline

1)

  The length relates to the common DALI control cable. The maximum values are rounded off and relate to the resistance values. 

EMC influences are not considered. For this reason, the values should be considered as absolute maximum values.

2)

  Both “normal” lamps as well as battery operated emergency lighting can be connected in a mixed configuration to the DGN/S 1.16.1. 

However, the maximum number of DALI devices may not exceed 64.

Summary of Contents for i-bus DGN/S 1.16.1

Page 1: ...he corresponding feedbacks the DGN S has the functions Staircase lighting Scene Sequence and Slave The lighting groups can be integrated in this way into a constant lighting control Function duration and partial duration tests and battery tests for the emer gency lighting systems with individual batteries to EN 62386 202 can be trig gered and stopped via KNX The test results are made available on ...

Page 2: ...C 160 mA 230 mA Temperature range operation storage transport 5 C 45 C 25 C 55 C 25 C 70 C Environmental conditions humidity maximum 93 moisture condensation should be excluded Design modular installation device MDRC dimensions mounting width mounting depth modular installation device Pro M 90 x 72 x 64 5 mm H x W x D 4 modules at 18 mm 68 mm Installation on 35 mm mounting rail to EN 60 715 Mounti...

Page 3: ...ilable free of charge at www abb com knx The ETS and the current version of the device application program are required for programming The current version of the application program is available for download on the internet at www abb com knx After import in the ETS it is available in the ETS under ABB Lighting DALI Switch Dim Emergency 1f DALI The device does not support the closing function of ...

Page 4: ...N_V1 0 2CDC 507 115 D0201 8 8 Circuit diagram Dimension drawing 2CDC 072 014 F0011 1 Label carrier 2 Button KNX 3 LED KNX 4 Connection terminal KNX 5 LED DALI fault 6 LED Gateway ON 7 Gateway operating voltage 8 Output DALI 9 Button DALI 10 DALI device without with function emergency lighting with individual battery 2CDC 072 012 F0011 ...

Reviews: