ABB HVL 120-0.3 Operating Manual Download Page 8

 

Operating manual HVL 120-0.3 

 

Assembly 

 

 

Assemble the fixing bracket for the low voltage limiter and the T-bracket 
for the cable connection according to the illustration. 

For this purpose, use the supplied M12x20 stainless steel bolts and 
tension washers. 

Tighten the bolts to a torque of 25 Nm. Use a suitable torque wrench for 
this purpose. 

The low voltage limiter is now pre-assembled and can be installed at 
the intended position in the network. 

 
 

Installation 

 

 

Before beginning the work, check the safety distance to adjacent live parts or 
equipment. If there is a danger of inadvertent touching, the 5 safety rules for 
establishing and securing the de-energised condition at the work location must be 
carried out (see the section entitled Safety instructions). 

 

 

 

 
Secure yourself against falling, if the intended mounting position is on a mast or on a 
high-level structure. For this purpose, use a secure working platform and wear your 
personal protective equipment.

 

 
The contact surface, to which the low voltage limiter is to be fitted by means of the fixing bracket, must be flat 
and clean. 
The mounting position of the low voltage limiter can be freely chosen. It must be noted, however, that the 
type plate and serial number should remain easily readable without removing the low voltage limiter. Polarity 
reversal is not possible owing to the bipolar design. 
The cable connection should be maintained as short as possible, since the protective effect of the low 
voltage limiter (especially in the case of fast-acting processes which can occur, for example, from the effects 
of lightning) is greatly influenced by this length dimension. 
The cross section of the cable connection must be constructed in compliance with the national regulations 
and the requirements of the railway network operator. 
 
 

Putting into service 

 
No further action or work is required at the installation location to put the equipment into service.  

1HC0023892 AA 

EN 

Page 8 / 12

 

Summary of Contents for HVL 120-0.3

Page 1: ...L DATA DESIGN 4 5 OPERATION AND STRUCTURE 6 6 ASSEMBLY AND INSTALLATION 7 7 MAINTENANCE SERVICING 9 8 SQS CERTIFICATE 11 9 EU DECLARATION OF CONFORMITY 11 Published by Contact details ABB Switzerland Ltd Phone 41 58 585 29 11 Surge arresters Telefax 41 58 585 55 70 Jurastrasse 45 E mail sales sa ch abb com CH 5430 Wettingen 1 www abb com arrestersonline Switzerland Subject to change without notice...

Page 2: ...of installation ABB accepts no liability for direct or indirect damage arising from the use or misuse of this product 2 DESCRIPTION AND FUNCTION Stationary installations for the supply of railway traction current employ the rails amongst other means as the return path for the traction current In the case of DC current railways electrically conductive parts or structures located in the area of the ...

Page 3: ...miter Each consignment is accompanied by final inspection record Scope of supply Low voltage limiter Fixing bracket for the low voltage limiter T bracket for cable connection Bolts and tension washers Final inspection record 1 x 1 x 1 x 4 x 1 x Following delivery each consignment must be checked for completeness and correctness compare against the order and delivery documents In the case of incomp...

Page 4: ...s current value in the stated time period the low voltage limiter resets itself back to its starting condition after responding If the current is higher than this or if the time period is greater than that stated the resetting capability cannot be guaranteed If the low voltage limiter does not reset to its starting condition it becomes permanently conductive In this way the protective function con...

Page 5: ...l HVL 120 0 3 Up Residual voltage at nominal discharge current In No HA Serial number Dimensions Low voltage limiter T bracket for cable connection Fixing bracket for the low voltage limiter 1HC0023892 AA EN Page 5 12 ...

Page 6: ... voltage U applied to the low voltage limiter and typically lies in the region of several hundred microseconds The duration of the overvoltage is therefore the controlling factor for the value of the voltage limitation If the duration lies in the region of several hundred microseconds then the characteristic curve of the metal oxide varistor alone defines the voltage limitation for example 380 V a...

Page 7: ...r must only be assembled installed and operated with the supplied accessories for its intended purpose and in accordance with its specifications o Modifications and repairs to the low voltage limiter itself and to its mounting parts are prohibited o If special problems arise which were not covered or were insufficiently covered in this operating manual please contact ABB Schweiz Before beginning a...

Page 8: ...ure For this purpose use a secure working platform and wear your personal protective equipment The contact surface to which the low voltage limiter is to be fitted by means of the fixing bracket must be flat and clean The mounting position of the low voltage limiter can be freely chosen It must be noted however that the type plate and serial number should remain easily readable without removing th...

Page 9: ...ltage limiter should be cleaned For this we recommend that a soft cloth is used with warm water and a mild household cleaner do not use solvents or abrasive cleaning agents Faults and reserve equipment The low voltage limiter is a protective equipment element and therefore overloading can never be completely excluded Depending on the number of units in operation it is recommended that a suitable n...

Page 10: ...under Point 1 and Point 2 must be repeated 4 The HVL 120 0 3 must be shorted out with a conductor of sufficient dimensions observe the national regulations and the requirements of the railway network operator This conductor must be arranged to ensure that detachment of the connection during removal of the HVL 120 0 3 cannot occur 5 Take a further measurement of the voltage via the connections of t...

Page 11: ...red and brought into service in conformity with the EC directive 73 23 EEC Company ABB Switzerland Ltd Surge arresters Jurastrasse 45 CH 5430 Wettingen Switzerland The following EC directives and harmonised standards have been applied EC directive 73 23 EEC low voltage electrical equipment The following European standards have been applied Railway applications stationary installations DC current s...

Page 12: ...Operating manual HVL 120 0 3 1HC0023892 AA EN Page 12 12 ...

Reviews: