![ABB GSB 800 Installation And Maintenance Manual Download Page 17](http://html.mh-extra.com/html/abb/gsb-800/gsb-800_installation-and-maintenance-manual_5363017.webp)
TR A N S FOR M E R BUS H I NG S T YPE G S B 8 0 0
I N S TA L L AT I O N A N D M A I N T EN A N C E G U I D E
17
Tightening nut
a
b = a + 9 mm
Tightening nut
11. Apply a generous amount of Molykote Multilub
(art. no. 1236 0011-127) on the nut, washer and draw-rod
bolt. Remove any excess Molykote Multilub with a rag.
12. Tighten the nut to 20 Nm and measure the distance a,
from the top of the nut to the top of the draw-rod bolt.
13. Continue tightening the nut until the measured distance
b = a + 9 mm. Each turn corresponds to an extension of
2 mm.
14. Continue at section 2.11 to ground the bushing flange.
WARNING
If the measured distance b = a + 9 mm is not
achieved before reaching 160 Nm, this indicates that
the threads are too poorly lubricated. If the threads
are not damaged, remove the nut and draw-rod bolt
to apply more Molykote Multilub and tighten again.
If the threads are damaged, the nut and draw-rod
bolt must be replaced.
Please contact the supplier if the specified values cannot be
attained after following the instructions above.
—
22 Measure the distance a.
—
23 Measure the distance b.