background image

Trouble-Shooting

The following guide is provided for trouble-shooting and isolating common problems. It does not cover every possible Solution

Contact Support Center at 800-843-3742 if any problem is not resolved by these procedures. 

I. 

The Shunt Trip accessory 

will not insert completely 
into the breaker. 

2. 

The breaker will not trip 

when control power is 
applied to the Shunt Trip. 

3. 

The breaker closes 

manually when the Shunt 
Trip with Lockout is 
energized. 

4. 

The breaker will not close 

manually when the Shunt 
Trip or Shunt  Trip  with 
Lockout control power is 
removed. 

5. 

The breaker fails to close 

after control power is 
removed from the Shunt Trip 
with Lockout. 

Possible  Cause

The accessory is inserted 
incorrectly. 

The Shunt Trip is not energized. 

The installed Shunt Trip has an 
incorrect voltage rating. 

The transformer connections are 
incorrect. 

The Shunt Trip connection is poor. 

The breaker is not closed. 

The Shunt Trip with Lockout solenoid 
is not energized. 

The Shunt Trip with Lockout control 
power connection is poor. 

The Shunt Trip or Shunt Trip with 
Lockout control power is actually still 
applied. 

The breaker is already closed

The Shunt Trip with Lockout plunger 
is not retracted. 

Control power was not removed for a 
minimum  of  0.25  seconds  before  the 
breaker was closed. 

Corrective  Action 

Ensure that the accessow is inserted in the correct slot, as in Figure 

2, and  that  the  label is upright. 

Check that Shunt Trip control power is applied at greater than 55% 
of the rated ac voltage. Check that the accessory is completely 
inserted; reinsert if necessary. 

Check for the proper voltage rating on the Shunt Trip. 

Ensure that steps 6, 7, and 8 in the Installation section have been 
followed correctly. 

Check that the Shunt Trip accessory is completely inserted. Check 
that the Trip Unit is seated correctly. If the Trip Unit was removed to 
set the switches, check that it has been correctly installed; remove 
and reinstall, if

 

 necessary.

Note that an otherwise underpowered Trip Unit would be powered

 

up by an energized Shunt Trip accessory. 

Verify that the breaker is closed. 

Check that the Shunt Trip with Lockout control power is applied at 
greater than 55%  of the rated ac voltage. Check that the accessory 
is completely inserted; re-insert if necessary. 

Note that an otherwise underpowered Trip Unit is powered by an 
energized Shunt Trip accessory. 

Check that the Shunt Trip with Lockout accessory is completely 
inserted. 

Check that the Shunt Trip or  Shunt  Trip with Lockout control 
power has been removed. 

Check that the breaker is not closed; if so, open it and try again. 

Remove the Shunt Trip with Lockout accessory. If the lockout 
plunger protrudes out of the accessory, replace the accessory. If 

 

the 

plunger does not protrude, reinsert the accessory, ensuring good 
alignment of the accessory in the pocket. 

Wait at least    0.25 seconds before closing the breaker after removing 
control power from the Shunt Trip. 

Symptom

1SQC930034M0201, GEH6519 

 

December

 2019

 

ABB Inc. 

 

305 Gregson Drive

 

Cary, NC 27511. 

electrification.us.abb.com

  

 

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With 
regard to purchase orders, the agreed 
particulars shall prevail. ABB Inc. does not 
accept any responsibility whatsoever for 
potential errors or possible lack of 
information in this document. 

We reserve all rights in this document and 
in the subject matter and illustrations 
contained therein. Any reproduction or 
utilization of its contents – in whole or in 
parts – is forbidden without prior written 
consent of ABB Inc.  
Copyright© 2019 ABB  
All rights reserved 

 

GE is a trademark of GE. Manufactured 
by ABB Inc. under license from GE. 

6

.

7

.

8

.

If a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit 
is installed, check that the Trip Unit display is active 
(powered).

Remove power from the Shunt Trip with Lockout.

 

Attempt to close the breaker; it should close as normal.

After the breaker has tripped and with the power still 
applied  to  the  Shunt  Trip  with  Lockout,  attempt  to 
close  the  breaker.  The  breaker  should  not  close  nor 
attempt to close.

I

f  a  Shunt  Trip  with  Lockout  has  been  installed,

 

continue 

with the following steps:

5

.

4

Summary of Contents for GE SPST480

Page 1: ...Trip and Shunt Trip with Lockout Installation The Shunt Trip and Shunt Trip with Lockout accessories shown in Figure1 can be installed in 800 4000 ampere frame Power Break II circuit breakers These accessories allow the breaker to be tripped electrically from a remote location In addition to providinga trip signal to the breaker the Shunt Trip accessories can be set up to interact with other Power...

Page 2: ...urs The configuration can be changed by removing the Trip Unit from the breaker setting the DIP switcheson the rear of the Trip Unit and reinstallingthe Trip Unit Figure 4 illustrates the Trip Unit rear DIP switches and their functions Table 4 lists the switch functions and the factory settings for each Use the followingprocedure to installthe Shunt Trip accessory into the Shunt Trip slot of the a...

Page 3: ...dure 1 Turn off the power to the Shunt Trip 2 Close the breaker contacts 3 Apply at least 55 of the rated ac voltage to the Shunt Trip the breaker should trip immediately 4 If a Bell Alarm Alarm Only or Bell Alarm with Lockout is present ensure that they activate or do not activate as selected by the MicroVersaTrip Plus or MicroVersa Trip PM Trip Unit DIP switches Figure 4 Accessory switch on the ...

Page 4: ...ip Unit would be powered up by an energized Shunt Trip accessory Verify that the breaker is closed Check that the Shunt Trip with Lockout control power is applied at greater than 55 of the rated ac voltage Check that the accessory is completelyinserted re insert if necessary Note that an otherwise underpowered Trip Unit is powered by an energized Shunt Trip accessory Check that the Shunt Trip with...

Reviews: