ABB GE ReliaGear Pro-Stock A2 Quick Start Manual Download Page 6

6

R E LI AG E A R LI G HTI NG PA N E LBOA R DS - PRO -STOCK A 2 CI RCU IT B R E A K E R K ITS , 24 0 VAC

1TQC213000E0021,

APR

202

1

ABB Inc.

305 Gregson Drive
Cary, NC 27511 

©Copyright 2020 ABB. All rights reserved. 
Information provided is subject to change without notice. Please verify all details with ABB. All values are design or typical 
values when measured under laboratory conditions, and ABB makes no warranty or guarantee, express or implied, that such 
performance will be obtained under end-use conditions.
Pro-Stock is a trademark and ReliaGear is a registered trademark of ABB Inc.
GE is a registered trademark used under license from General Electric company.

electrification.us.abb.com

Figure 7.  Installation of a Pro-Stock A2 three-phase, six-pole circuit breaker kit, catalog 

number MBA16, into a ReliaGear 400 A or 600 A lighting panelboard.

Summary of Contents for GE ReliaGear Pro-Stock A2

Page 1: ...10 32 x 3 8 N722EP16006B6 4 4 Nut and Washer 5 16 18 N269P23B6 3 7 Circuit Breaker Base 1 19 A2 Breaker Subassembly 30015700940G14 1 10 Label MAIN 315A7337P1 1 Table 3 Parts list for the 240 Vac A2 three phase six pole breaker installation kit catalog number MBA16 Item Description Part Qty 1 Shield Insert 139C5504P189 1 2 Thread Rolling Screw and Washer 315A7034P3 6 3 Screw 10 32 x 3 8 N722EP16006...

Page 2: ... for three phase protruding from the circuit breaker base over the two or three bolts in the bus bars of the interior assembly Secure with two or three 5 16 18 nuts 4 tightened to 100 120 lb in 6 Drop the breaker subassembly 19 Align the Z strap on the breaker assembly over the strap inside the plastic base Hand tighten self rolling screw 2 to locate the breaker assembly On the other side align th...

Page 3: ...R KITS 240 VAC Figure 2 Removing the shield inserts from the shield for a subfeed breaker installation in 400 A or 600 A panels Figure 1 Attaching the shield insert to the shield for a main breaker installation in all panels or a subfeed breaker in 225 A panels ...

Page 4: ...AC Figure 4 Typical installation of a subassembly Pro Stock breaker kit catalog number MBA12 Figure 3 Typical installation of a subassembly Pro Stock breaker kit catalog number MBA13 and MBA16 Tightening Torques for Figure 3 4 Fastener ID Torque Value lb in H1 9 11 H2 64 78 ...

Page 5: ...tion of a Pro Stock A2 three phase three pole circuit breaker kit catalog number MBA13 into a ReliaGear 400 A or 600 A lighting panelboard Figure 5 Installation of a Pro Stock A2 single phase two pole circuit breaker kit catalog number MBA12 into a ReliaGear 400 A or 600 A lighting panelboard ...

Page 6: ...values when measured under laboratory conditions and ABB makes no warranty or guarantee express or implied that such performance will be obtained under end use conditions Pro Stock is a trademark and ReliaGear is a registered trademark of ABB Inc GE is a registered trademark used under license from General Electric company electrification us abb com Figure 7 Installation of a Pro Stock A2 three ph...