background image

AMP1 

Analog_value objects

Use the Present_Value property of the Analog_Value object for 
all writable variables in the meter other than those used 
specifically for BACnet configuration or Time Synchronization 
(in the Device Object) or Data Logging (in the Trend_Log 
objects).

Values are checked when written, and errors are returned for 
invalid entries. This table describes how the meter uses those 
variables, what values are valid, and what their defaults are. 
When writing values to the Present_Value properties of 
Analog_Value BACnet objects, there is a delay of up to about 

two seconds to validate and store the new value. An 
immediate read of the same property before that delay has 
elapsed can return the prior value (even if the new value was 
accepted). To read a value immediately after writing it, check 
the Reliability property first. When it reports a No_Fault_
Detected status, the Present_Value of the object is current.

These objects support the Description and Reliability object 
properties and all required Analog_Value object properties, 
but Present_Value is the only writable property.

20

A M P1  I NTEG R ATE D  POWE R  A N D  E N E RGY 

I N S TA L L AT I O N  I N S T R U C T I O N S

For troubleshooting or service related questions, contact ABB at 800-782-8061 or at [email protected]

No.

Name

Description

R/W NV

Units

Range

Factory
Default
Value

Additional information

AV1

Config

Configuration R/W –

n/a

n/a

Always
returns
”0”
when
read

Command Register:

– Write 30078 (0x757E) to clear all energy accumulators to 0 (All).
–  Write 21211 (0x52DB) to begin new Demand Sub-Interval 

calculation cycle and log another data value on Trend_Log objects 
TL1-TL3 (when the meter is in Manual “Sync-to Comms” mode). This 
takes effect at the end of the next 1 second calculation cycle. Write 
no more frequently than every 10 seconds.

–  Write 21212 (0x52DC) to reset Max Demand values to Present 

Demand Values. Takes effect at the end of the next 1 second 
calculation cycle. Write no more frequently than every 10 seconds.

– Write 16498 (0x4072) to clear pulse counters to 0.

AV2

System_
Type

System Type

R/W NV

n/a

40, 31, 12, 11, 
10

40

System_Type:

– Write 10 for Single-Phase: A + N
– Write 11 for Single-Phase: A + B
– Write 12 for Split-Phase: A + B + N
– Write 31 for 3-Phase Á: A + B + C, no N
– Write 40 for 3-Phase Y: A + B + C + N

AV3

CT_Ratio_
Primary

CT Ratio -
Primary

R/W NV

Amps

5-32000

200

Current Transducer Size – Primary Current Range
(Default is set for 100 A CTs)

AV4

CT_Ratio_
Secondary

CT Ratio -
Secondary

R/W NV

1/Volts

1,3

3

Current Transducer Type – Secondary Interface

– Enter 1 for CTs with 1V outputs (Default)
– Enter 3 for CTs with 1/3V outputs

AV5

PT_Ratio

PT Ratio

R/W NV

Value

0.01 - 320.0

1

Potential Transformer Ratio – The default is 1.00 (1:1), which is no PT 
attached. Set this value before setting the System Voltage (below).

AV6

System_
Voltage

System
Voltage

R/W NV

Volts

from 82 (times 
the PT_Ratio in 
AV5) to 660 
(times the PT_
Ratio in AV5 –
absolute limits 
are 82-32000)

480

System Voltage – This voltage is Line to Line unless in System Type 10 (in 
object AV2), in which case it is Line to Neutral. This value is used to by 
the meter to calculate the full scale power for the analog outputs and 
pulse configuration (see below), and as full scale for phase loss (in 
object AV8). Do not set the meter to voltages outside the range of 82-
660 volts times the PT Ratio in object AV5.

AV7

Display_
Units

Display Units

R/W NV

n/a

0,1

1

Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, 
VA)

AV8

Phase_Loss_
Voltage_
Threshold

Phase Loss
Voltage
Threshold

R/W NV

Percent

1-99

10

Phase Loss Voltage Threshold in percent of System Voltage (in object 
AV6). Default is 10 (10%). Any phase (as configured in AV2) whose level 
drops below this threshold triggers a Phase Loss alert – i.e. if the System 
voltage is set to 480 V L-L, the L-N voltage for each phase should be 277 
V. When the threshold is set to 10%, if any phase drops more than 10% 
below 277 V, (less than 249 V), or if any L-L voltage drops more than 10% 
below 480 V (less than 432 V) the corresponding phase loss alarm bit 
will be true.

AV9

Phase_ Loss_
Imbalance_
Threshold

Phase Loss
Imbalance
Threshold

R/W NV

Percent

1-99

25

Phase Loss Imbalance Threshold in Percent. Default is 25% phase to 
phase difference. For a 3-phase Y (3 + N) system type (40 in object AV2), 
both Line to Neutral and Line to Line voltages are tested. In a 3-phase Á 
System type (31 in object AV2), only Line to Line voltages are examined. 
In a single split-phase (2 + N) system type (12 in object AV2), only the line 
to neutral voltage are compared.

AV10 Subintervals

Number of
Subintervals
Per Demand
Interval

R/W NV

1-6

1

Number of Sub-Intervals per Demand Interval. Sets the number of sub-
intervals that make a single demand interval. For block demand, set this 
to 1. Default is 1. When Sub-Interval Length (in object AV11) is set to 0 
(sync-tocomms mode), the meter ignores this value.

AV11

Subinterval_
Length

Subinterval
Length

R/W NV

hundreths 
of a 
second

0, 10-32767

90000

Sub-Interval Length in hundredths of a second. For sync-to-comms 
mode, which allows manual triggerring of demand intervals and the 
logging of another Trend_ Log record, set this value to 0 and write 21211 
to the reset register (object AV1) each time the sub-interval must be 
externally reset. Default is 90000 (15 minutes). This variable is tied 
directly to the Log_Interval property of all three Trend_Log objects 
(their value is always the same as this one). Changing any of these four 
properties changes all of them.

Summary of Contents for GE ReliaGear AMP1

Page 1: ...INSTALLATION INSTRUCTIONS ReliaGear lighting panelboard AMP1 integrated power and energy ...

Page 2: ......

Page 3: ...information 13 User interface for setup 15 RS 485 communications 15 Display screen diagram 16 Quick setup 17 BACnet default settings 17 BACnet programming information 19 Device object 20 Analog_value objects 21 Analog_input objects 23 Binary_input objects 24 Data logging 25 Trend_log objects 26 Installation 27 Supported system types 28 Troubleshooting AMP1N4 29 Enclosure for AMP1 series energy met...

Page 4: ...d for certain critical control functions provide a means to achieve a safe state during and after a path failure Examples of critical control functions are emergency stop and over travel stop This symbol indicates an electrical shock hazard exists Documentation must be consulted where this symbol is used on the product DANGER Hazard of Electric Shock Explosion or Arc Flash Failure to follow these ...

Page 5: ...600V L L 347V L N CE maximum 300V L N DC 3W maximum UL and CE 125 to 300 VDC Ride Through 100 msec 120VAC Input Pulse Solid state or mechanical contacts currents less than 1 mA 2 pulse inputs Minimum Pulse Width 20 msec Output RS 485 Port 2 wire 1200 to 38400 baud Modbus RTU Mechanical Weight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front displate IP20 meter Display Characteristics B...

Page 6: ... The LCD screen on the faceplate allows instant output viewing The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022 It can be mounted with any orientation over the entire ambient temperature range either on a DIN rail or in a panel The AMP1H5 meter is not sensitive to CT orientation to reduce installation errors Data output Full Data Set FDS Pow...

Page 7: ...only The red alarm LED lights when any of the 3 phase voltages drop below the selected threshold The green Energy LED lights when the pulse 1 input contacts are active or closed 1234 5 kWh Alarm Energy Pulse Inputs RS 485 BACnet X2 A X1 X2 B X1 X2 C X1 IA IB IC X2 X1X2 X1X2 X1 CT Inputs1 or 0 333 VAC CONTROL POWER 0 1A 50 60 Hz 12 VA VB VC Neutral Earth Control Power UL 90V L N 600VL L CE 90VL N 3...

Page 8: ...n CT no PT USE SYSTEM TYPE 31 3L Figure 5 3 phase 4 wire wye direct voltage input connection 3 CT USE SYSTEM TYPE 40 3L 1n Figure 6 3 phase 4 wire wye connection 3 CT 3 PT USE SYSTEM TYPE 40 3L 1n X2 X1 X2 X1 N A B C White Black White Black X2 X1 L1 L2 L3 C A B N A B C X2 X1 X2 X1 White Black White Black White Black X2 X1 X2 X1 X2 X1 White Black Whi Blac W White Black X2 X1 N L1 L2 L3 X2 X1 X2 X1 ...

Page 9: ... L2 L3 G 1 2 L1 G 1 2 L2 L3 N L1 L2 L3 G 1 2 1 2 G N L1 L2 L3 G 1 2 L1 G 1 2 L2 L3 N L1 L2 L3 G 1 2 1 2 G N L1 L2 L3 G 1 2 Control power transformer CPT connection The control power transformer may be wired L N or L L Output to meet meter input requirements Fuse recommendations Keep the fuses close to the power source obey local and national code requirements For selecting fuses and circuit breake...

Page 10: ...rce 6 30 VAC AMP1B1 and AMP1Cx AMP1B1 only 3 30 VDC Power source 6 30 VAC 3 30 VDC Power source 6 30 VAC Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A A Amps UAB UBC UAC VAB VBC VAC Voltage Line to Line V VLN Voltage Line to Neutral PF PF Power Factor U VLL Voltage Line to Line HZ HZ Frequency KSh KV...

Page 11: ... DEMND Demand Scroll When Idle To SETUP APHAS BPHAS CPHAS A KWh 3 KWh B KWh C KWh _PHAS HZ ENRGY To ALERT Energy Accumulators and Counters ENRGY PULS1 PULS2 KWh Accumulated Real Energy Ph Volts Line Line U Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Total Reactive Power Q Total Apparent Power S Accumulated Real Energy Frequency Power Factor Average of ...

Page 12: ...ck Display none if no alerts To Setup Setup Meter Reset Data PhaseLoss A B C LowPower Factor A B C Frequency Out ofRange A Current Out of Range Voltage Out of Range A BC A B C INFO MODEL OS SN RS Serial Number Reset Operating System System ALERT INFO PLOSS A b C LOWPF A bC FERR A I OVR A b C V OVR A bC PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configurator E...

Page 13: ...or wiring diagrams This value must be set before the System Voltage if used Set system voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to calculate the theoretical maximum system power and as the reference voltage for setting the Phase Loss threshold Maximum is 32000 Volts For system type 1 N 10 this is a Line to Neutral Voltage indicated by V LN Note the met...

Page 14: ...on For system types with neutral the Line to Neutral voltages are also tested For system types 1 N 10 and 2 11 imbalance is not tested Set demand interval INTRV The number of Sub Intervals 1 to 6 in a Demand Interval Default is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Set display units to switch between IEEE VLL VLN W VAR VA Un...

Page 15: ...tion resistors at each end of the bus not included Shield is not internally connected to earth ground Connect shield to earth ground somewhere on the RS 485 bus only at one point For all terminals on AMP1 Series meters When tightening terminals apply the correct torque 0 37 0 44 ft lb 0 5 0 6 N m Use 14 24 gauge 2 1 0 2 mm2 wire S Red Black Gray 0 37 to 0 44 ft lb Use 14 to 24 gauge wire 0 5 to 0 ...

Page 16: ...Exit the screen to the right 4 Use or buttons to select the parameter to configure 5 If the unit has an RS 485 interface the first Setup screen is S COM set communications a Press to go to the ADDR screen and through the address digits Use or to select the Modbus address b Press to accept the value and go to the BAUD screen Use or to select the baud rate c Press to go to the PAR screen Use or to s...

Page 17: ...eading the Present_Value of the 15 Binary_ Input objects or as a group by reading the Present_Value of Analog_Input object 52 Alerts are not latched and do not generate events to system They indicate presence of these conditions at the time they are read but the device does not latch and store them until they are read if the condition changes before they are read the alert will go away All Analog_...

Page 18: ... May only write values such that AV6 AV5 is from 82 to 660 absolute range is 82 32000 To ensure AV6 accepts rejects the proper values set AV5 first AV7 May only write values 0 and 1 AV8 May only write values from 1 to 99 AV9 May only write values from 1 to 99 AV10 May only write values from 1 to 6 AV11 May only write the value 0 or a value from 1000 to 3276700 in multiples of 100 The Record_Count ...

Page 19: ...racters Default value is Installed location not yet identified Description R NV GE AMP1H5 Energy Meter S N serial number Protocol_Version R NV 1 BACnet Protocol Version 1 Protocol_Revsion R NV 4 BACnet Protocol Revision 4 Local_Date R Date Set via BACnet Time Synchronization only reverts to Jan 1 2000 if control power drops Local_Time R Time Set via BACnet Time Synchronization only reverts to 12 0...

Page 20: ...V Value 0 01 320 0 1 Potential Transformer Ratio The default is 1 00 1 1 which is no PT attached Set this value before setting the System Voltage below AV6 System_ Voltage System Voltage R W NV Volts from 82 times the PT_Ratio in AV5 to 660 times the PT_ Ratio in AV5 absolute limits are 82 32000 480 System Voltage This voltage is Line to Line unless in System Type 10 in object AV2 in which case it...

Page 21: ...Real Power Phase A R kW 0 Max_Power AI45 AV10 kW_B Real Power Phase B R kW 0 Max_Power AI45 AV11 kW_C Real Power Phase C R kW 0 Max_Power AI45 AI12 PF_A Power Factor Phase A R Power Factor 0 00 1 00 1 00 for 100 AI13 PF_B Power Factor Phase B R Power Factor 0 00 1 00 1 00 for 100 AI14 PF_C Power Factor Phase C R Power Factor 0 00 1 00 1 00 for 100 AI15 Volts_AB Votlage Phase A B R Volts AI16 Volts...

Page 22: ...WH_A Real Energy Consumption Phase A R NV kWh 0 3 4 E38 AI43 KWH_B Real Energy Consumption Phase B R NV kWh 0 3 4 E38 AI44 KWH_C Real Energy Consumption Phase C R NV kWh 0 3 4 E38 AI45 Max_Power Theoretical Maximum System Power R NV kW 0 1 84467e19 Theoretical Maximum System Power This is the theoretical maximum power the meter expects to see on a service It is calculated by the meter from the Sys...

Page 23: ...e Phase B R 0 INACTIVE 1 ACTIVE Phase B Current out of range BI6 Current_Error_A Current Out of Range Phase C R 0 INACTIVE 1 ACTIVE Phase C Current out of range BI7 Frequency_Error Frequency Error R 0 INACTIVE 1 ACTIVE Phase A Frequency out of range BI8 Reserved_BI8 Reserved R 0 INACTIVE 1 ACTIVE Returns INACTIVE BI9 Phase_Loss_A Phase Loss Phase A R 0 INACTIVE 1 ACTIVE Phase Loss Phase A voltage ...

Page 24: ...wer Present Demand AI34 Present_Value The Log_Interval Demand Subinterval can be set from 10 seconds to 32767 seconds values of 1000 to 3276700 The subinterval timer which determines how often the meter s demand accumulators are updated also triggers writing to the Trend_Log log buffers Use the Log_Interval property to set the data logging time subinterval in units of hundredths of a second 0 01 s...

Page 25: ...d in hundredths of a second Default is 90000 15 minute intervals minimum value is 1000 10 seconds This property can also be set to Zero which will change all three Trend_Logs and the Demand calculation to a manual mode sometimes referred to as Sync to Comms In manual mode the demand interval is updated and another record is logged upon a manual command which is issued by writing the value 21211 to...

Page 26: ...e electrical enclosure near equipment to be monitored Do not install on the load side of a Variable Frequency Drive VFD Clip flush with outside edge Snap onto DIN rail Insert clips from inside Screw mounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside The stopping pegs must face the housing and the screw hole must be exposed on the ou...

Page 27: ...ch are to be ignored and if neutral is connected Setting the correct System Type prevents unwanted energy accumulation on unused inputs selects the formula to calculate the Theoretical Maximum System Power and determines which phase loss algorithm is to be used The phase loss algorithm is configured as a percent of the Line to Line System Voltage except when in System Type 10 and also calculates t...

Page 28: ...CTs and PTs to verify correct connection to the same service PT polarity and adequate powering See the Wiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter address is incorrect Verify that the meter is correctly addressed see Setup section Power meter baud rate is incorrect Verify that the baud rate of the meter matches that o...

Page 29: ...s received safety training to recognize and avoid the hazards involved NEC2011 Article 100 No responsibility is assumed by manufacturer for any consequences arising out of the use of this material Control system design must consider the potential failure modes of control paths and for certain critical control functions provide a means to achieve a safe state during and after a path failure Example...

Page 30: ...elements The enclosure is equipped with DIN rail mounting hardware for easy installation and a NEMA 4X rating for durability The swing panel kit and multiple locking options provide additional security from unwanted tampering Dimensions Product components 1 Enclosure 2 DIN rail 3 Hinged lid 4 Clasp 5 Brackets for swing panel cover 6 Swing panel cover 7 Mounting feet Hardware not pictured 4 25 108 ...

Page 31: ...ing and the black clip must protrude slightly past the bottom edge 2 Mount the AMP1N4 enclosure to a wall or panel Cut holes in the enclosure for wire conduit connections prior to the installation of the meter in the enclosure After running the wiring seal all holes properly to maintain the enclosure rating If using metallic conduit bonding between the conduit connections is not automatic and must...

Page 32: ...d previously Wire the meter according to the instructions in the meter installation guide Push the top of the meter onto the DIN rail Push the bottom of the meter onto the DIN rail until there is an audible click If necessary remove the meter from the DIN rail using a flat screwdriver to pry out the bottom black clip while lifting out the bottom of the meter AMP1N4 Installation Lower the four brac...

Page 33: ... and secure the clasp to close Screws are provided to secure the hinged lid Local codes may require this step to prevent opening by unauthorized persons if a locking mechanism is not used For added security the installer may attach a locking mechanism AMP1N4 Installation Optional Attach locking mechanism here not included Optional Use included hardware to secure the hinged lid at all four corners ...

Page 34: ...34 AMP1 INTEGR ATED POWER AND ENERGY INSTALL ATION INSTRUCTIONS This page left blank intentionally ...

Page 35: ...AMP1 INTEGR ATED POWER AND ENERGY INSTALL ATION INSTRUCTIONS 35 This page left blank intentionally ...

Page 36: ...e lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Inc 2022 ABB All rights reserved ABB Inc 305 Gregson Drive Cary NC 27511 United States electrification us abb com...

Reviews: