3 Installation
Wechsel ein-auf zweispaltig
3.1 Installation
Requirements
The device measures the flowrate in both directions. The factory
default is forward flow, as shown in Fig. 3.
G00156
Fig. 3
The following items must be observed:
3.1.1 Electrode
axis
Electrode axis (1) should be horizontal if at all possible or no more
that 45° from horizontal.
G00041
max. 45°
1
Fig. 4
3.1.2 In- and outlet pipe sections
Straight inlet section
Straight outlet section
≥
3 x DN
≥
2 x DN
DN = Flowmeter primary size
•
Do not install fittings, manifolds, valves etc. directly in front of the
meter tube (1).
•
Butterfly valves must be installed so that the valve plate does not
extend into the flowmeter primary.
•
Valves or other turn-off components should be installed in the
outlet pipe section (2).
•
For compliance with the measuring accuracy, observe the inlet
and outlet pipe sections.
G00037
1
2
3xDN
2xDN
Fig. 5
3.1.3 Vertical
connections
•
Vertical installation for measurement of abrasive fluids, flow
preferably from below to above.
G00039
Fig. 6
3.1.4 Horizontal
connections
•
Meter tube must always be completely full.
•
Provide for a slight incline of the connection for degassing.
G00038
3°
Fig. 7
3.1.5 Free inlet or outlet
•
Do not install the flowmeter at the highest point or in the draining-
off side of the pipeline, flowmeter runs empty, air bubbles can
form (1).
•
Provide for a siphon fluid intake for free inlets or outlets so that
the pipeline is always full (2).
G00040
1
2
Fig. 8
3.1.6 Installation in the vicinity of pumps
•
For flowmeter primaries which are to be installed in the vicinity of
pumps or other vibration generating equip-ment, the utilization of
mechanical snubbers is advantageous.
G00043
Fig. 9