Replacing the FB module in PROFIsafe network
1. Replace the FB module according to the instructions in
FPNO-21 PROFINET
fieldbus adapter module user's manual
(3AXD50000158614 [English]), or
FENA-01/-11/-21 Ethernet adapter module user's manual
(3AUA0000093568
[English]).
2. Assign the device name for the FB module from the safety PLC (see section
Configuring the ABB AC500-S Safety PLC
on page
or section
Siemens SIMATIC Fail-safe S7 PLC
on page
.
3. Update the revision and the serial number of the new FB module to the logbook of
the driven machine.
Replacing the FSE module
1. Disconnect the encoder connector and power supply connector, then remove the
FSE module.
2. Replace the FSE module according to the instructions in
FSE-31 pulse encoder
interface module user's manual
(3AXD50000016597 [English]).
3. Update the revision and the serial number of the new FSE module to the logbook
of the driven machine.
Replacing the safety encoder
1. If the new encoder is not identical with the old encoder: Make sure that the
encoder meets the requirements in section
on page
2. Install the new encoder according to the installation instructions given by the
encoder manufacturer and the instructions given in the FSO-21 module and
FSE-31 module user's manuals.
3. Make sure that the safety encoder related parameter settings in FSO-21 module,
for example, pulse count, are set according to the new encoder.
4. Do the start-up and validation procedures. See section
on page
Start-up and validation test
1. Do the start-up procedure according to chapter
.
2. Do the validation procedure for each safety function according to chapter
.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...