Safety functions 51
FSO modes
The FSO can be in one of the following modes:
•
Power down:
The power to the FSO is off. The drive STO circuit is open. The
POWER LED is off.
•
Start-up
: The FSO is starting up after power-up. Indicated with a blinking green
RUN LED.
•
Running
: The FSO is up and running. It can be in different states (see section
on page
) depending on the status of safety functions and the
safety fieldbus communication. Indicated with a green RUN LED.
•
Fail-safe
: There is a failure in the FSO. The drive STO is active. Indicated with a
red STATUS/FAULT LED. You have to reboot the FSO to exit the Fail-safe mode.
•
Configuration
: Parameters are uploaded from the FSO module. The drive STO
is active. Indicated with blinking RUN and STATUS/FAULT LEDs. You can exit the
Configuration mode by downloading the new configuration to the FSO or by
rebooting the FSO.
For more information on the FSO LEDs, see section
on page
FSO states
When the FSO is up and running, it can be in one of the following states depending
on the drive STO status:
•
Safe
: STO active, that is, the drive STO circuit is open and the motor is stopped.
The SBC is active (if used).
•
Operational
: STO inactive.
In the Operational and Safe states, the FSO can execute the safety functions.
Note
: When the POUS function is active, the FSO module is in the Operational state
and the drive STO is active.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...