140 PROFIsafe
Remote I/O control
You can control the FSO module outputs and read input information also from the
safety PLC. A request to activate or deactivate an output is sent from the safety PLC
(PROFIsafe controller) to the FSO module in a PROFIsafe message. See section
on page
Only FSO outputs that are not configured for any control use (for example, to control
an indication lamp or a brake) can be activated from the safety PLC. If the safety PLC
tries to activate an FSO output that is configured for control use, the FSO module
rejects the request, activates the SSE function and goes into the Fail-safe mode (see
section
). To exit the Fail-safe mode,
remove the power from the FSO or reboot the FSO with drive parameter
96.09 FSO
reboot
.
FSO module passivation
If the FSO module or the safety PLC detects an error in the fieldbus communication,
the FSO module is passivated. The status of the FSO outputs that are not configured
for any control use (for example, to control an indication lamp or a brake) are set to
“low”. The FSO module activates the SSE function, goes into the Safe state and
generates an event. The user can select the event type (warning, fault or event) with
parameter
After the cause of the passivation has been detected, the SSE function must be
acknowledged before the communication continues. The status of the safety
functions and FSO outputs are set according to the PROFIsafe message that was
received before the passivation.
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...