Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

Register address when the ABB Drives - Classic communication profile is used.

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh

.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source

FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed)

50.02

FBA A comm loss func

Fault

51.02

Profile

The ABB Drives - Classic communication profile is the default value.

51.03

Station ID

Set the address of the device.

51.04

Baud rate

Set the baud rate of the link.

51.05

Parity

Set the use of parity and stop bit(s) and the data length.

Register Address

Register Data (16-bit)

(4)00001

ABB Drives Profile Control Word

(4)00002

Reference 1

(4)00003

Reference 2

(4)00004

ABB Drives Profile Status Word

(4)00005

Actual 1

(4)00006

Actual 2

(4)00101…(4)09999

Drive Parameter Access (16-bit); Register Address = (4)00000 + 100 × Group + Index

(4)20000…(4)29999

Drive Parameter Access (32-bit); Register Address = (4)20000 + 200 × Group + 2 × Index

See the latest version of 

FSCA-01 RS-485 adapter module 

user's manual

 (3AUA0000109533 [English]) in ABB library 

(

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

Pin allocation for [X1]

Bus termination with [J2]

Pin

 Description

1

SHDL

Bus cable shield

2

DATA_A Data 

positive 

3

DATA_B

Data negative

4

GND_B

Isolated signal ground

     Termination activated     Termination deactivated

 

3AXD50000158546 Rev A (EN) 2017-11-23

FSCA-01 manual

Fieldbus communications web page