ABB FPNO-21 Quick Installation And Start-Up Manual Download Page 2

Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh

.

Connectivity configuration

The FPNO-21 adapter module has a web page for connectivity configuration.

To access the web page:

1. Open a web browser and type the IP address of the adapter module in the address field. 

The IP address is visible in group 51, parameters 5...8 

Example

: http://192.168.0.24/

2. Log in with a user name and a password.

The default user name: admin
Password: The last six digits of the MAC address of the adapter module, in upper case letters, 
without hyphens. The MAC ID is visible on the front cover of the adapter module.

Example

: If the MAC address of the adapter module is 00-1C-01-00-2F-73, the password is 002F73.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source

FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.

50.02

FBA A comm loss func

Fault

51.02

Profile

The ABB Drives communication profile is the default value.

52.01

FBA A data in1

SW 16bit

52.02

FBA A data in2

Act 16bit

53.01

FBA A data out1

CW 16bit

53.02

FBA A data out2

Ref1 16bit

See the latest version of 

FPNO-21 PROFINET adapter 

module user's manual

 (3AXD50000158614 [English]) in 

ABB library (

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

 

3AXD50000158577 Rev A (EN) 2017-11-23

FPNO-21 manual

Fieldbus communications web page