![ABB FPNO-21 Quick Installation And Start-Up Manual Download Page 2](http://html.mh-extra.com/html/abb/fpno-21/fpno-21_quick-installation-and-start-up-manual_2720002.webp)
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par refresh
.
Connectivity configuration
The FPNO-21 adapter module has a web page for connectivity configuration.
To access the web page:
1. Open a web browser and type the IP address of the adapter module in the address field.
The IP address is visible in group 51, parameters 5...8
Example
: http://192.168.0.24/
2. Log in with a user name and a password.
The default user name: admin
Password: The last six digits of the MAC address of the adapter module, in upper case letters,
without hyphens. The MAC ID is visible on the front cover of the adapter module.
Example
: If the MAC address of the adapter module is 00-1C-01-00-2F-73, the password is 002F73.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source
FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
50.02
FBA A comm loss func
Fault
51.02
Profile
The ABB Drives communication profile is the default value.
52.01
FBA A data in1
SW 16bit
52.02
FBA A data in2
Act 16bit
53.01
FBA A data out1
CW 16bit
53.02
FBA A data out2
Ref1 16bit
See the latest version of
FPNO-21 PROFINET adapter
module user's manual
(3AXD50000158614 [English]) in
www.abb.com/drives/documents
)
.
new.abb.com/drives/connectivity/fieldbus-connectivity
).
3AXD50000158577 Rev A (EN) 2017-11-23