Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par refresh
.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source
FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed)
50.02
FBA A comm loss func
Fault
51.02
Node address
Set the node address of the module according to the network configuration.
51.05
Profile
The ABB Drives communication profile is the default value.
52.01
FBA A data in1
SW 16bit
52.02
FBA A data in2
Act 16bit
53.01
FBA A data out1
CW 16bit
53.02
FBA A data out2
Ref1 16bit
See the latest version of
FPBA-01 PROFIBUS DP adapter
module user's manual
(3AFE68573271 [English]) in ABB
library (
www.abb.com/drives/documents
)
.
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
(
new.abb.com/drives/connectivity/fieldbus-connectivity
).
Connection procedure
It is recommended to use a PROFIBUS-
approved D-SUB 9 connector. These
connectors have a built-in termination network
and inductors for station capacitance
compensation.
Connect the cable to the D-SUB connector as
shown in this figure.
1A 1B 2A 2B
Gr
een
Re
d
Gr
een
Re
d
OUT
IN
Grounding clamp/
Strain relief
3AXD50000158188 Rev A (EN) 2017-11-23
FPBA-01 manual