Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh

.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source

FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed)

50.02

FBA A comm loss func

Fault

51.02

Node address

Set the node address of the module according to the network configuration.

51.05

Profile

The ABB Drives communication profile is the default value.

52.01

FBA A data in1

SW 16bit

52.02

FBA A data in2

Act 16bit

53.01

FBA A data out1

CW 16bit

53.02

FBA A data out2

Ref1 16bit

See the latest version of 

FPBA-01 PROFIBUS DP adapter 

module user's manual

 (3AFE68573271 [English]) in ABB 

library (

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

Connection procedure

It is recommended to use a PROFIBUS-
approved D-SUB 9 connector. These 
connectors have a built-in termination network 
and inductors for station capacitance 
compensation.

Connect the cable to the D-SUB connector as 
shown in this figure.

1A 1B 2A 2B

Gr

een

Re

d

Gr

een

Re

d

OUT

IN

Grounding clamp/ 
Strain relief

 

3AXD50000158188 Rev A (EN) 2017-11-23

FPBA-01 manual