Communication profiles 85
Status word contents
The table below shows the contents of the Status word for the ABB
Drives communication profile. The upper case boldface text refers
to the states shown in the state machine on page
.
10
REMOTE_
CMD
1
Fieldbus control enabled.
0
Control word and reference not getting
through to the drive, except for CW bits
OFF1, OFF2 and OFF3.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2.
Effective if control location parameterized
to be selected from fieldbus.
0
Select External Control Location EXT1.
Effective if control location parameterized
to be selected from fieldbus.
12…
15
Drive-specific (For information, see the drive documentation.)
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
RDY_RUN
1
READY TO OPERATE
0
OFF1 ACTIVE
2
RDY_REF
1
OPERATION ENABLED
0
OPERATION INHIBITED
3
TRIPPED
1
FAULT
0
No fault
4
OFF_2_STA
1
OFF2 inactive
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 inactive
0
OFF3 ACTIVE
6
SWC_ON_
INHIB
1
SWITCH-ON INHIBITED
0
–
Bit
Name
Value
STATE/Description
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...