Start-up 55
Starting up ACS380, ACS580 and ACS880 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive with parameter
50.01 FBA A enable
.
The selection must correspond to the slot where the adapter
module is installed. For example, if the adapter module is
installed in slot 1, you must select slot 1.
3. With parameter
50.02 FBA A comm loss func
, select how the
drive reacts to a fieldbus communication break.
Note:
This function monitors both communication between the
fieldbus master and the adapter module and communication
between the adapter module and the drive.
4. With parameter
50.03 FBA A comm loss t out
, define the
time between communication break detection and the selected
action.
5. Select application-specific values for parameters
50.04
…
50.11
. Examples of appropriate values are shown in
the tables below.
6. Set the FEPL configuration parameters in group
51
.
•
Select the communication profile with parameter
51.02
.
•
Configure the network settings with parameters
51.03
and
51.04
.
7. Save the valid parameter values to permanent memory with
parameter
96.07
Parameter save
.
8. Validate the settings made in parameter group
51
with
parameter
51.27 FBA par refresh
.
9. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Summary of Contents for FEPL-02 Ethernet POWERLINK
Page 4: ......
Page 10: ...10 Table of contents ...
Page 20: ...20 About the manual ...
Page 28: ...28 Mechanical installation ...
Page 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Page 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Page 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Page 90: ...90 Communication profiles ...
Page 100: ...100 Communication protocol ...
Page 104: ...104 Diagnostics ...
Page 108: ...108 Technical data ...