Connection procedure

1. Connect the network cables to connectors [X1] and [X2] on the module. 

2. Connect the cable from the master to the left port [X1].

3. In the line topology, if there are more slave devices in the same line, connect the next slave device to 

the right port [X2].

Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh

.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.

50.02

FBA A comm loss func Fault

51.02

Profile

The CANopen device profile (CiA 402) is the default value.

See the latest version of 

FEPL-02 Ethernet POWERLINK 

adapter module user's manual

 (3AUA0000123527 

[English]) in ABB library (

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

 

3AXD50000158164

 

Rev A (EN) 2017-11-23

FEPL-02 manual

Fieldbus communications web page