Connection procedure

1. Connect the bus cable to the BNC connectors [A] and/or [B] on the module. Use both connectors in 

redundant operation, otherwise use either connector [A] or [B].

2. Terminate the ControlNet bus line with a 75-ohm resistor.

Start-up

When the module is connected to the drive, the drive control program sets the applicable parameters. 
See the appropriate drive manual.

Basic parameter settings

To take the settings into use, validate and refresh the parameters with parameter 

51.27 FBA par refresh.

Set the node address of the device with the rotary switches on the module.

Further information

Index

Name

Value

20.01

Ext1 commands

Fieldbus A

22.11

Speed ref1 source

FBA A ref 1

28.11

Frequency ref1 source FBA A ref 1

50.01

FBA A enable

Enable (or select the option slot in which the module is installed)

50.02

FBA A comm loss func Fault

51.02

Profile

The ODVA AC/DC drive profile is the default value.

See the latest version of 

FCNA-01 ControlNet adapter 

module user's manual 

(3AUA0000141650 [English]) in 

ABB library (

www.abb.com/drives/documents

)

.

For more information on fieldbus options and protocols 
provided by ABB Drives, see the fieldbus 
communications web page 
(

new.abb.com/drives/connectivity/fieldbus-connectivity

).

 

3AXD50000158201 Rev A (EN) 2017-11-23