Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par refresh
.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source
FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
50.02
FBA A comm loss func
Fault
51.04
IP configuration
Set the IP address according your network configuration.
51.05...08
IP address
51.09
Subnet CIDR
51.14
Device obj ID lo
Set a unique device object instance value for BACnet devices.
51.15
Device obj ID hi
See the latest version of
FBIP-21 BACnet/IP adapter
module user's manual
(3AXD50000028468 [English]) in
ABB library (
www.abb.com/drives/documents
)
.
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
(
new.abb.com/drives/connectivity/fieldbus-connectivity
).