![ABB FAIO-01 User Manual Download Page 18](http://html.mh-extra.com/html/abb/faio-01/faio-01_user-manual_2711018.webp)
General cabling instructions
Use 0.5 … 2.5 mm
2
twisted pair shielded cable with an applicable
voltage rating.
Do not route signal cables parallel to power cables.
Wiring
Connect the external control cables to the applicable module
terminals.
■
Connection example for motor winding temperature
measurement
This example shows how to connect three Pt100 sensors for motor
temperature measurement between the analog inputs and outputs.
Do not connect both ends of the cable shields directly to ground. If
a capacitor cannot be used at one end, leave that end of the shield
unconnected.
XAI1+
XAI1-
XAO1+
XAO1-
T
T
T
18 Installation
30
Summary of Contents for FAIO-01