Connect power wires to switch terminals
and attach ground wire to the ground
terminal block inside the enclosure.
Reference the National Electric Code
and all local codes for appropriate wire
size and grounding requirements.
Close the enclosure door. Note that both
the switch and the operating handle on the
door must be in the OFF position. Tighten
the lock’s screw.
A00233A
Pozi-drive #2 or flat blade
screwdriver
eOT520_, eOT530_, eOT540_:
Torque 7 lb-in, 0.8 Nm
eOT560_, eOT580_ :
Torque 18 lb-in, 2 Nm
Auxiliary contacts:
Torque 7 lb-in, 0.8 Nm
Ground terminal
block:
Torque
10.6-12.3 lb-in
1,2-1,4 Nm
eOT520_, eOT530_, eOT540_:
9-10 mm
0.35-0.39 in
eOT560_, eOT580_ :
10-12 mm
0.39-0.47 in
eOT520_, eOT530_, eOT540_:
0.75...10 mm
2
18...8 AWG
eOT560_, eOT580_ :
1.5...35 mm
2
14...4 AWG
A0
71
99
A0023
4A
1
2
EN C LOSED M A N UA L M OTO R CO N T R O L L ER S , EOT5 2 0 – 5 8 0
7
—
Wiring