EGNL Series Vandal Resistant Emergency Light
1/2
© 2020 ABB. All rights reserved.
EGNL Series Vandal Resistant Emergency Light
AC, AC/DC and Self-powered
Use Flexible Conduit Only
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always
be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. All servicing should be performed by qualified service personnel.
2. Disconnect power at fuse or circuit breaker before installing or servicing.
3. All electrical connections must be in accordance with local codes,
ordinances and the National Electric code.
4. All unused wires must be capped to prevent shorting.
5. Do not use outdoors.
6. Do not let power supply cords touch hot surfaces.
7. Do not mount near gas or electric heaters.
8. Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
9. The use of accessory equipment not recommended by the manufacturer
may cause an unsafe condition.
10. Do not use this equipment for other than intended use.
11. Use caution when handling batteries (self-powered only).
12. Allow battery to charge for 24 hours before first use (self-powered only).
SAVE THESE
INSTRUCTIONS
Installation Instructions
1. Turn off AC power.
2. Feed AC unswitched circuit of rated voltage into junction box and leave 6”
of wire length.
3. Using a flat head screwdriver, insert the blade into the slots and tilt to
release the latch and open the front cover (see figure 1).
4. Push in the locking clips located on each side of the reflector and remove
the reflector assembly (see figure 1).
Wall and Ceiling Mount
1. Remove the appropriate knockouts in the back plate.
2. Feed AC wires through the center hole into the back plate.
3. Mount and secure the back plate to the junction box. Ensure the gasket is
compressed tightly to the surface.
4. Make the proper connections according to model configuration:
For self-powered see figure 3.
For AC, AC/DC see figure 4.
5. Attach safety cable from housing to reflector assembly.
6. Connect battery connector to PCBA.
7. Reattach reflector assembly. Push in the locking clips located on each side
of the reflector and snap in reflector assembly (see figure 1).
8. Adjust LED strips as required (see figure 6).
9. Snap in the lens.
Note: for units with auto-test option, ensure button on lens aligns with
test switch on reflector.
IMPORTANT:
Maximum mounting height: 22 feet from floor.
WARNING:
Risk of Shock.
Disconnect Power before Installation and Maintenance.
Figure 1
Reflector locking clip location
Slot location
to open front cover
Back plate
Wire nuts
Gasket
Reflector
Figure 2
Figure 3
Red
White (Neutral)
Black (120 to 347VAC)
Wall switch
Battery
LED 1
LED 2
Test
LED
Wiring diagram for self-powered models
PCBA
indicator
switch
With wall switch
Without wall switch
Red
White (Neutral)
Black (120 to 347VAC)
Battery
LED 1
LED 2
PCBA
Connect the black and red wires to hot lead, white wire to the neutral as
shown below.
Connect the black wire to 120/347Vac, white wire to the neutral.
Connect the red wire to one contact of the wall switch and conect the
other contact to the black wire as shown below.
Test
LED
indicator
switch