ABB EDS500 Series Operating	 Instruction Download Page 4

The command line interface

The command line of the 500NMD11 is similar to the

(DOS) command line known from the PC. All device

properties can be set and shown here.

Commands are typed into the console, pressing

< { E n t e r } >

 will start execution.

Commands can be abbreviated as soon as they

are unambiguous, i.e. 

< s h   s y >

 is equivalent

to 

< s h o w   s y s t e m >

< s e   s w   p 1   n   s >

is equivalent to 

< s e t   s w i t c h   p o r t 1   n o

s h u t d o w n >

.

A command overview can be listed on every level by

typing 

< ? >

. Example: 

< s h   s y   ? >

 translates to

< s h o w   s y s t e m   ? >

 and results in 

s n m p   s n t p

s s h   s y s l o g   t e m p e r a t u r e

 being shown

as command keywords to follow, i.e. one possible

command is 

< s h o w   s y s t e m   t e m p e r a t u r e >

.

There are two authentication levels on the

command line: Login authentication and Enable

authentication. Login authentication can be

described as a read only mode and is accessible

directly after establishing a serial connection

with the PC. Enable authen-tication is required

once you need to change system settings or

show the complete system parameter set.

Enable authentication is reached by entering

the 

< e n a b l e >

 command. Both authentication

levels can be protected by a password, the

respective commands are 

< s e t   l o g i n p a s s

{ s t r i n g 2 0 } >

 and 

< s e t   e n a b l e p a s s

{ s t r i n g 2 0 } >

.

Configuration commands entered on the

command line interface are stored in the running

configuration of the device, which represents the

current state of the system. To preserve this status

after a reboot, the running configuration must

be transferred to the startup configuration using

the command 

< w r i t e >

. During system startup

all commands from the startup configuration

are being executed and thus create the running

configuration. When a configuration stick is

attached to the device, executing the 

< w r i t e >

command results in the running configuration

being copied not only to the startup configuration

but also to the stick configuration (unless the stick

is set to “read only”). During system startup with

attached config stick, the stick configuration over-

writes the startup configuration.

The current configuration (running configuration)

can be displayed using the command 

< s h o w

r u n n i n g - c o n f i g >

 (only with Enable

authentication). The start configuration may be

shown using 

< s h o w   s t a r t u p - c o n f i g >

.

When a config stick is attached, its content can be

shown using 

< s h o w   s t i c k - c o n f i g   >

.

Interface configuration
SHDSL interfaces

The DSL interfaces of the 500NMD11 work as point-
to-point connections over two-wire copper lines.
One side needs to be configured as master, the other
one as slave. The current master/ slave setting is
indicated through the interface’s “Master” LED on the
front panel and can be displayed using the command

< s h o w   i n t e r f a c e   { d s l 1   |   d s l 2 } >

respectively. To change the master / slave setting use

< s e t   i n t e r f a c e   { d s l 1   |   d s l 2 }   m o d e

m a s t e r >

 and 

< s e t   i n t e r f a c e   { d s l 1   |

d s l 2 }   m o d e   s l a v e >

.

In delivery status, the speed of the DSL interfaces
defaults to 192 kbps. However, depending on wire
length, condition of the line and the desired signal
quality, signif-icantly higher speed rates can be
achieved.

Signal quality (SHDSL.bis)

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

35

30

25

20

15

10

5

0

11400 kbps

10240 kbps

8192 kbps

5696 kbps

4096 kbps

3072 kbps

2048 kbps

1536 kbps

1024 kbps

768 kbps

512 kbps

256 kbps

192 kbps

[km]

[dB]

Figure 2: Signal quality with 0,8mm cable diameter, no additive noise

After activating interfaces on both sides of the line
using the command 

< s e t   i n t e r f a c e   { d s l 1   |

d s l 2 }   n o   s h u t d o w n >  

 automatic connection

establishment will be initiated (this setting is already
activated when in delivery status). Depending on
line length, line condition and speed settings, this
procedure might need some time and several attempts
before a successful connection can be established. The
negotiation phase is signaled through the front panel
LEDs: the DSL activity LED is blinking while DSL link
LED is off.

Generally automatic speed negotiation is configured
on the less accessible end of the DSL line (

< s e t

i n t e r f a c e   { d s l 1   |   d s l 2 }   s p e e d   a u t o >

or 

< s e t   i n t e r f a c e   { d s l 1   |   d s l 2 }   s p e e d

e x t - a u t o >

, see following table), while a fixed speed

value is applied to the better reachable end of the line.

Local setting

Remote setting

Speed: local

fixed, remote

auto

192, 256, 512,

768, 1024, 1280,

1536, 1792, 2048,

2304

auto

Speed: local

fixed remote

fixed

192... 2304, step

size 8 kbps

192... 2304, step

size 8 kbps

Speed: local

fixed, remote

ext-auto

192, 256, 512,

768, 1024, 1280,

1536, 1792, 2048,

2304, 2560, 3072,

3584, 4096,

4608, 5120, 5696

ext-auto

Speed: local

fixed, remote

fixed

192...11400, step

size 8 kbps

192...11400, step

size 8 kbps

Table 1:

Speed settings for the DSL interfaces

With matching interface speed configuration and after
successful connection negotiation (signaled through
the DSL link LEDs) the status of the connection
(including the signal quality) can be shown using

Summary of Contents for EDS500 Series

Page 1: ...t interface can operate at transmission rates of 10 or 100 Mbps depending on the connected devices in half duplex or full duplex mode The operation mode is detected and set automatically by the EDS500...

Page 2: ...n 1 2 B Input 3 B Output 4 GND 5 A Input 6 1 6 A Output Power connector X1 The EDS500 devices are equipped with a wide range power supply for voltages between 24 and 60 Volts DC power consumption see...

Page 3: ...y as well as from remote In the following some methods are introduced for a complete description please see EDS500 Manual Part 2 Functions 1KGT151021 Configuration using a serial configuration cable I...

Page 4: ...ig Interface configuration SHDSL interfaces The DSL interfaces of the 500NMD11 work as point to point connections over two wire copper lines One side needs to be configured as master the other one as...

Page 5: ...possible to define logical sub nets for different applications for instance one subnet for RTU communication an other subnet for voice over IP The interfaces can be configured as trunk or access port...

Page 6: ...t during restart Safety DANGER Interrupt the power supply before mounting or dismounting the device WARNING An easy to access manual interrupter has to be installed into the power feed of the modem to...

Page 7: ...purchase orders the agreed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights i...

Reviews: