13.Setup
The actuator only requires the basic settings (adaptation to the operating range) in order to be operated
with the standard or custumer specific configuration. Use the Local Control Panel (LCP) for these set-
tings. Use the appropriate configuration software for more detailed parameter changes or diagnosis
functions.
13.1Set-up via local control panel (LCP)
13.1.1Operating elements
1. Write-protect switch
(Default setting: OFF)
2. LED for 100% position
Indication if adjustment procedure, saved position, or fault by different
flash frequencies.
3. Drive buttons
Press to cause drive motion
4. Reset button
Press to restart processor
5. Power LED
Indicates available mains supply
6. RS 232 socket
Connection socket to PC
7. Potential toggle switch
Connection of reference potential to the system or protective earth (by
default set to system) of electronic unit
8. LED for 0% position
Indication if adjustment procedure, saved position, or fault by different
flash frequencies..
9. Accept button (0%)
Press to define current position as 0%; simultaneously press push but-
ton 9 + 10 to complete the adjustment procedure.
10. Accept button (100%)
Press to define current position as 100%; simultaneously press push
button 9 + 10 to complete the adjustment procedure
Figure 25: Local Control Panel (LCP)
The actuator range is not preset in factory!
13.1.2Setup procedure
-
Undo the screws of the LCP cover
-
Swing the cover to the side
13.1.3Initial situation
-
Electronics connected to power supply and actuator
-
Write-protect switch (1) set to “OFF” position
-
Electronics in operating mode “MAN” (no signal on DI 1)
-
No fault (if a fault occurs, both LEDs flash alternately at 4 Hz)
1
2
3
4
5
6
7
8
9
10
(r0110rxa)