S O LUZI O N I PA SS I V E , AT T I V E E P R E V EN T I V E

Technical Specifications 

Technical Specifications for Hardware

Nominal Operating Voltage

15/27 kV

Rated Max. Voltage

27 kV

Rated Power Frequency

60 Hz

Rated Continuous Current

200 A

Rated Symmetrical Interrupting Current

8 kA

Rated Short-Time Withstand Current

8 kA

Rated Short-Time Withstand Duration

0.5 s

Rated Peak-Withstand Current

20.8 kA

Rated BIL

125 kV

Rated Power Frequency Wet Withstand (60s)

60 kV

Creep Distance H1 to H2

668 mm

Recloser Unit Weight

20 KG (44 Lbs)

Auxiliary Power

12V DC (for programming)

Operating Temperature

-40C to +60C

Rated Number of Operations

10,000 Operations

Ingress Protection

IP65

Standards Compliance

IEEE C37.60/IEC 62271-111

Technical Specifications for Electronics & Software

Modes of Operation

Autorecloser
Sectionalizer
Breaker/Switch

Rated operating duty

Min O 0.2s CO 2s CO 2s CO Lockout 
Max O 5s CO 5s CO 20s CO Lockout

Minimum Pickup Fault Current

10 A

Minimum current for Wi-Fi communication

5 A (

1

)

Minimum Power-Up Time

25 ms

Protection Functions

50/51P (

3

)

Other Functions

2

nd

 Harmonic Inrush Restraint

Cold Load Pickup
Non-Reclose/Hot Line Tag
Switch On To Fault

Current Sensor Accuracy

> 50A: ±1%
> 20A: ±2.5%
> 10A: ±5%
< 10A: ±1.6A

Operating Curves  

ANSI/IEC, Recloser, Fuse and Custom Curves

Records

Events and Fault Records (1000)
Internal Device Events (100)
Disturbance Records (250)
Load Profile (60 days)
Security Log (1000)

Communication

Wi-Fi with WPA2 128 Bit-Encryption

Auto Disable Feature
Hide SSID Feature

(1) Tripping/Reclosing capability is not dependent of availability of certain minimum pre-fault current. 
Minimum current noted is for connecting to the unit wirelessly.

Summary of Contents for Eagle

Page 1: ... Maximum protection Maximum uptime Maximum peace of mind Self Powered Single Phase Recloser for up to 27kV Eagle ...

Page 2: ... Maximizing Reliability with a Safe Reliable and Simple Solution ...

Page 3: ... Interface 007 No Arcing Design 008 Battery Free Operation 009 Hassle Free and Secure Wi Fi Communication 010 Mounting 011 Technical Specifications 012 013 Dimensions 014 015 Software Features 016 Ordering Guide 017 Accessories 018 Service Support ...

Page 4: ...rectly to the pole as a new installation or a replacement to oil filled single phase reclosers It can be installed separately on single phase laterals or in a group of three for a three phase lateral circuit Eagle recloser drastically improves the reliability indices for utilities simply by eliminating the sustained interruptions experienced by the customers due to fuse blowing schemes and momenta...

Page 5: ...t H2 Aux Power 12VDC Vent Connection Disconnection Ring Operating Handle Open Close Reset Lockout Embedded Vacuum Interrupter Non Reclose HLT Handle Wi Fi Activation Operations Counter Recloser Position Indicator Light Sensor for Wi Fi Activation option to enable via NR handle Lockout Beacon LED up to 12hrs after Lockout ...

Page 6: ...d and fault currents This provides a highly accurate measurement for protection as well as load profiling Since it is not a conventional CT saturation is not a concern at the highest fault current levels Mount Latching Mechanism The Eagle has a latching mechanism on the H1 terminal that latches to the mounting clip The fuse clip and the latch ensure that the Eagle does not drop open unless it is e...

Page 7: ...ing occurs in vacuum interrupter prior to disconnection and closing happens in vacuum interrupter after connection CLOSE VI CLOSE VI New Installation in 4 steps Reclosing after Lockout in 3 steps Manual Opening with Visual Break in 3 steps 1 Prepare 1 Open 1 Fix Fault 3 Connect 3 Visual Break 3 Close 2 Hang 2 Disconnect 2 Reset 4 Close RESET LOCKOUT ...

Page 8: ... and operational inefficiency inspired a completely battery free design on the ABB Eagle The recloser consists of a mechanical closing mechanism which can be utilized to manually close the recloser using the main operating handle Battery Free Manual Mechanical Closing Eliminates Battery performance and replacement concerns Costly battery replacement programs Stocking shelf life and inventory of ba...

Page 9: ...ss steps to meet utility specific guidelines without compromising security 128 Bit encryption with WPA2 level security System level cyber security implementation Security logs with accurate timestamp Wi Fi network access options Always keeping Wi Fi network ON Auto disable Wi Fi after 15 minutes of inactivity configurable time Re activation of Wi Fi using light pulses no hot stick required OR Re a...

Page 10: ...phase can be mounted on the same pole for a three phase configuration Crossarm Mounted Fuse Cutout Replacement Easily replace an existing fuse cutout by using a 20 double insulator mount or simply add the ABB Eagle in parallel to the existing cutout with the fuse tube removed DIMENSION A REPLACEABLE COOPER RECLOSERS 12 Type E 4E V4E 4H V4H L V4L 11 25 Type D 23 25 Type DV A A Double Insulator with...

Page 11: ...ications for Electronics Software Modes of Operation Autorecloser Sectionalizer Breaker Switch Rated operating duty Min O 0 2s CO 2s CO 2s CO Lockout Max O 5s CO 5s CO 20s CO Lockout Minimum Pickup Fault Current 10 A Minimum current for Wi Fi communication 5 A 1 Minimum Power Up Time 25 ms Protection Functions 50 51P 3 Other Functions 2nd Harmonic Inrush Restraint Cold Load Pickup Non Reclose Hot ...

Page 12: ...le Recloser Dimensions 26 0 660 14 9 378 1 50 38 1 100 19 3 490 9 9 7 245 H1 Terminal AUX Power H2 Terminal Mechanical position indicator Operation counter Flashing LED lockout indicator HCEP Embedded vacuum interrupter Mechanically operated OPEN CLOSE handle ...

Page 13: ... 19 29 9 39 11 85 16 14 6 56 4 25 21 072 92 2 535 24 166 75 108 08 317 5 300 9 152 40 101 60 301 8 489 9 238 6 410 0 11 25 11 85 300 9 11 88 9 39 16 14 25 58 12 50 301 8 489 9 19 29 238 6 285 8 410 0 649 8 317 5 95 0 3 74 676 8 782 9 30 82 649 8 25 58 285 8 11 25 238 6 9 39 92 2 3 63 301 8 11 88 26 65 727 7 28 65 863 9 34 01 166 75 108 08 6 56 4 29 535 2 21 07 667 3 26 27 754 4 29 70 410 0 16 14 9...

Page 14: ... eye view on device status Carry out operations right from the dashboard Single Line Diagram with recloser status Compatible with all web browsers on all platforms including hand held devices Self Supervision Operation counter diagnostics and wear monitoring alarms Security Log Record of logins changes and unauthorized access attempts Role Based Access Permissions based on user roles 1 Viewer Log ...

Page 15: ...Tag Modes Toggling the non reclose handle triggers the recloser into non reclose hot ling tag mode By default Eagle enters the non reclose mode when the NR handle is engaged It uses the fastest available tripping curve to trip and then stops auto reclosing Alternatively if hot line tag settings are enabled the recloser enters hot line tag mode when the NR handle is engaged The protection can be ma...

Page 16: ...D30 Double Insulator 23 25 Mount C02 Double Insulator Crossarm Mount 20 Deg NNN No Mounting Frame A Arrester Bracket A Arrester Bracket Provided N No Arrest er Bracket E Animal Guards E Animal Guard for Eagle Mount Arrester M Animal Guard for Eagle Mount Only A Animal Guard for Arrester Only N No Animal Guards A Aux Power A 12VDC Aux Power Adapter 1 per 10 Z 12VDC Aux Power Adapter Custom Qty N No...

Page 17: ...17 Accessories Animal Guards for Eagle Disconnect Bypass Switch ...

Page 18: ...B customer service On site training commissioning assistance and migration training On site training sessions are offered upon request and can be arranged at the customer facility Arrangements may be made by contacting ABB in Lake Mary Florida ABB can provide commissioning assistance during installation including migration support for the development of settings ...

Page 19: ...19 ...

Page 20: ...y suitability or availability with respect to the information products services or related graphics contained in the document for any purpose Any reliance placed on such information is therefore strictly at your own risk ABB reserves the right to discontinue any product or service at any time Contact Us ABB Inc 680 Century Point Lake Mary FL 32746 Phone 1 407 732 2000 Customer service 1 800 929 79...

Reviews: