120
ACH550-UH User’s Manual
4021
ACT2 MAXIMUM
-1000…1000%
1%
100%
Sets the maximum value for
ACT
2.
• See 4018
ACT
1
MINIMUM
.
4022
SLEEP SELECTION
-6…7
-
0
Defines the control for the PID sleep function.
0 =
NOT
SEL
– Disables the PID sleep control function.
1 =
DI
1 – Defines digital input
DI
1 as the control for the PID sleep function.
• Activating the digital input activates the sleep function.
• De-activating the digital input restores PID control.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for the PID sleep function.
• See
DI
1 above.
7 =
INTERNAL
– Defines the output rpm/frequency, process reference, and process actual value as the control for the
PID sleep function. Refer to parameters 4025
WAKE
-
UP
DEV
and 4023
PID
SLEEP
LEVEL
.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for the PID sleep function.
• De-activating the digital input activates the sleep function.
• Activating the digital input restores PID control.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for the PID sleep function.
• See
DI
1(
INV
) above.
4023
PID SLEEP LEVEL
0.0…120.0
Hz /
0.1
Hz /
0.0
Hz
0…7200 rpm
1 rpm
Sets the motor speed / frequency that enables the PID sleep function – a motor speed / frequency below this level,
for at least the time period 4024
PID
SLEEP
DELAY
enables the PID sleep function (stopping the drive).
• Requires 4022 = 7
INTERNAL
.
• See figure: A = PID output level; B = PID process feedback.
4024
PID SLEEP DELAY
0.0…3600.0 s
0.1 s
60.0 s
Sets the time delay for the PID sleep function – a motor speed / frequency below 4023
PID
SLEEP
LEVEL
for at least
this time period enables the PID sleep function (stopping the drive).
• See 4023
PID
SLEEP
LEVEL
above.
Group 40: Process PID Set 1
Code Description Range
Resolution
Default
S
Start
t < P 4024
t
t > P 4024
t
Stop
P 4023
P 4025
P 4026
Setpoint
A
B
P 4025
Setpoint
P 4025
C
D
t
}
}
4005 = 1
4005 = 0