5.7.4
Dual input feed (optional version)
5.7.4.1
Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected
Fig 5.7.4.1-1: Dual input feed block diagram
5.7.4.2
Cable sections
Frame
type
UPScale
ST
Load
in kW
Input 3x400V/230V
Bypass 3x400V/230V
Output 3x400V/230V
@ cosphi 1.0
Battery
Fuse B
(Agl/CB)
Cable B (mm
2
)
(IEC 60950-1)
Max.
Input
Current
with
battery
charging
[A]
Fuse C
(Agl/CB)
Cable C
(mm
2
)
(IEC
60950-1)
Cable D
(mm
2
)
(IEC
60950-1)
I nom
[A]
Fuse E
+/N/-
(Agl/CB)
Cable E (mm
2
)
for CBAT UPScale 120 or
200 ONLY
+ / N / -
Com. Battery
Sep.
Battery
40
40
3x80A
5x16
68 A
3x80A
4x16
5x16
58 A
NOT ALLOWED
60
60
3x125A
5x35
102 A
3x125A
4x35
5x35
87 A
80
80
3x160A
5x50
136 A
3x160A
4x50
5x50
116 A
3x224A*1
3x95 *1
4x (3x10)
120
120
3x224A 4x95+1x50 (PE)
208 A
3x224A
4x95
5x70
174 A
3x300A*1
3x150 *1
6x (3x10)
200
200 3 x 350 A
5 x 185
333 A
3 x 350 A
4 x 185
5 x 185
290 A
3 x 450 *1 3 x (2 x 95)*1 5 x (3x25)
*1 only valid for common battery use
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...