Installation 

 

  Remove cover by releasing 2 off screws with a screwdriver. 

  Wiring to overload: 

  Connect leads provided from – terminal 14 to terminal 95 and terminal A2 to terminal 96 

  Check operating coil voltage and frequency 

  Remove appropriate top/bottom knockouts. Attach conduit bushes to conduit 

  Mount base and connect to bushes. If continuous grounding is required fit separate bonding strap. For on-site control 

circuit conversions see overleaf. 

  Connect cables and ensure that all terminals are tight.  

  When installed, set the hand/auto rest selector and adjust the current calibration to the desired value. 

  Replace cover and re-tighten cover screws. 

  Note: If an extra control device is required, see overleaf. 

 
 

Overload Selection 
 

Order references

 

Overload 
rating 
Full load A

 

Approximate motor rating 

Recommended 
max. fuse size for 
short circuit 
protection  A 

400V/3PH 
AC3 

230V/1PH 
 

 

 

 

 

 

Min. 

Max. 

kW 

hp 

kW 

hp 

TA25DU1.4 

1.0 

1.4 

0.37 

0.55 

0.07 

0.09 

TA25DU1.8 

1.3 

1.8 

0.55 

0.75 

0.1 

0.125 

10 

TA25DU2.4 

1.7 

2.4 

0.75 

1.0 

0.18 

0.25 

TA25DU3.1 

2.2 

3.1 

1.1 

1.5 

0.25 

0.33 

TA25DU4.0 

2.8 

4.0 

1.5 

2.0 

0.37 

0.5 

20 

TA25DU6.5 

4.5 

6.5 

2.2 

3.0 

0.55 

0.75 

TA25DU11 

7.5 

11.0 

4.0 

5.5 

1.1 

1.5 

35 

TA25DU14 

10.0 

14.0 

5.5 

7.5 

1.5 

2.0 

TA25DU19 

13.0 

19.0 

7.5 

10.0 

2.2 

3.0 

TA25DU25 

18.0 

25.0 

11.0 

15.0 

3.0 

4.0 

80 

TA25DU32 

22.0 

32.0 

15.0 

20.0 

4.0 

5.5 

 

Note: This product is not suitable for d.c. applications. 

 

 

Terminal capacity 

 
 

 

Main 

Auxiliary 

Contactor 

1 x 4mm

2

 

or 
2 x 2.5mm

2

 

1 x 4mm

2

 

or 
2 x 2.5mm

2

 

Overload 

1 x 10mm

2

 

or 
2 x 6mm

2

 

2 x 2.5mm

2

 

 

Summary 

 
A direct-on-line motor starter with ingress protection to 
IP66. Two-tone plastic enclosure with ABS lid and base. 

 
Trip class 10 requirements IEC 947-4-1 
 

1.05 x FLC 

No tripping 

1.2 x FLC 

Trip within 2 hours 

1.5 x FLC 

Trip within 4 minutes 

7.2 x FLC 

Trip between 4s and 10s 

 

NOTE: 

 FLC = Full load current

 

1

T

V

S

0

1

3

1

1

4

P

0

3

0

0

 R

e

v

1

 0

1

/1

 

DOL Starter  

Plastic Enclosure to IP65  
IEC947-4-1       Issue 1  