![ABB DNP31.0 Technical Description Download Page 17](http://html.mh-extra.com/html/abb/dnp31-0/dnp31-0_technical-description_4825017.webp)
- 17 -
Data sheet DNP31.0
Issue: 09.2015
Connection Object,
Instance 2 = Polled I/O Message Connection
, Attributes
Attribute
Access
Name
Type
Value
1
Get
State
USINT
*1)
2
Get
Instance Type
USINT
1 = I/O Connection
3
Get
Transport Class Trigger
BYTE
0x82 - Server,
Transport Class 2 *4)
4
Get
Produced Connection ID
UINT
01111xxxxxx *2)
5
Get
Consumed Connection ID
UINT
10xxxxxx101 *2)
6
Get
Initial Comm. Characteristics
BYTE
0x01
7
Get
Produced Connection Size
UINT
*3)
8
Get
Consumed Connection Size
UINT
*3)
9
Get/Set
Expected Packet Rate
UINT
in ms
12 (0x0C)
Get
Watchdog Timeout Action
USINT
0 = time out
13 (0x0D)
Get
Produced Conn. Path Length
UINT
6
14 (0x0E)
Get
Produced Connection Path
EPATH
20 04 24 64 30 03
15 (0x0F)
Get
Consumed Conn. Path Length
UINT
6
16 (0x10)
Get
Consumed Connection Path
EPATH
20 04 24 65 30 03
17 (0x11)
Get
Production Inhibit Time
UINT
0
*1) Connection state
0
nonexistent
1
configuring
2
wait for connection ID
3
established
4
timed out
5
deferred
*2) xxxxxx = node address
*3) The size of Produced and Consumed Connection depends on the device connected to the DNP31 (as
of writing UMC100.3). For detailed information, please refer to the device manual.
*4) If alloc_choice = polled and ack suppression is enabled then value = 0x80.