80
6 years preventive maintenance
Following additional actions have to take place:
−
Replace the cooling fans of units T1 … T5.
o
Exchange the cooling fans sizes T1 … T3 (two fans).
o
Exchange the cooling fans size T3 (four fans).
o
Exchange the cooling fans size T4.
o
The manufacturer’s estimation for the operational time of the classic cooling fans is:
o
3ADT754041P0001: 70,000 hours at 25°C.
o
DCA0012171P0001: 40,000 hours at 60°C.
o
3ADT754028P0001: 40,000 hours
at 60°C.
o
3ADT754042R0002: 40,000 hours at 40°C.
The mayor problem is the failure of the bearings. The cooling fans are used in:
Size Thyristor power controller Fan type
T1
DCT880-W0x-0035-07
DCT880-W0x-0055-0x …
DCT880-W0x-0125-0x
2 x 3ADT754041P0001 (internal 24 V
DC
)
T2
DCT880-W0x-0160-0x …
DCT880-W0x-0245-0x
T3
DCT880-W0x-0325-0x …
DCT880-W0x-0360-0x
DCT880-W0x-0420-0x
4 x 3ADT754041P0001 (internal 24 V
DC
)
T4
DCT880-W0x-0550-0x …
DCT880-W0x-0675-0x
1 x DCA0012171P0001 (230 V
AC
)
DCT880-W0x-0740-0x
1 x 3ADT754028P0001 (230 V
AC
)
T5
DCT880-W03-0890-0x …
DCT880-W02-0960-0x
1 x 3ADT754042R0002 (230 V
AC
)
Aging of the components result in:
1. Increased vibration due to the imbalance of the cooling fan (can last for several months).
2. Increased temperature due to the stopped cooling fan (drive trips with overtemperature).
−
Check the flat cables and their connections.
Preventive Maintenance
3ADW000449R0101 DCT880 Service Manual e a
Summary of Contents for DCT880
Page 1: ...DCT880 Service Manual DCT880 Thyristor power controller 20 A 4160 A ...
Page 2: ......
Page 85: ...85 T2 160 A 245 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 86: ...86 T3 325 A 420 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 87: ...87 T4 550 A 740 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 88: ...88 T5 890 A 960 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 89: ......