Accessories
133
3ADW000462R0401 DCS880 Hardware manual e d
RS232-Port
The RS232 interface is used for download the 'Field exciter firmware package'.
The firmware download is activated by setting S2:1-2 before the auxiliary voltage is switched ON.
Field exciter mode is S2:3-4 (default).
Diagnostics
All messages are sent to the armature converter and displayed in Signals 04.26, 04.27, 04.36 and
04.37. If the communication is broken or node numbers are mixed up the simple fault display on the
SDCS-FEX-4 can be used.
Therefore the unit is equipped with two small LEDs.
V730 = Green
V731 = Yellow
Following messages are displayed:
Both OFF
No 24 V supply
Green and yellow continuous
No firmware or S2:1-2
Green blinking
16 A / 25 A / 35 A output active, waiting for
DCSLink communication
Green continuous
16 A / 25 A / 35 A output active,
DCSLink communication OK
Yellow blinking
5 A output active (X100:2), waiting for
DCSLink
communication
Yellow continuous
5 A output active (X100:2), DCSLink communication OK
Green and yellow toggling:
,
,
X times yellow
Y times green
Warning or Fault
X = 1
Y = 1
Warning
Phase missing, see parameters 28.63 / 42.68
Y = 2
Warning
Temperature heatsink
Y = 6
Warning
Parameters added
Y = 7
Warning
Parameter up- or download failed
Y = 8
Warning
Compatibility
Y = 9
Warning
Parameters restored
X = 2
Y = 1
Fault
DCSLink communication
Y = 2
Fault
Supply voltage synchronization
Y = 3
Fault
Overcurrent
Y = 4
Fault
Fast voltage rise, see parameters 28.62 / 42.67
Y = 5
Fault
AC supply voltage < 30 V
AC
Y = 6
Fault
AC supply voltage > 650 V
AC
Y = 9
Fault
Temperature heatsink
Y = 10
Fault
Parameter flash read
Y = 11
Fault
Compatibility
Y = 12
Fault
Auxiliary voltage
Y = 14
Fault
General hardware (no reset possible)
Y = 15
Fault
General firmware (no reset possible)