![ABB DCS800 Installation Manual Download Page 22](http://html.mh-extra.com/html/abb/dcs800/dcs800_installation-manual_3333022.webp)
22
Fastening the Shipping Split to the Floor
Shipping Split to the Fastening the shipping split to the floor is especially important
in installations subject to vibration or other movement.
Fastening Clamps 3AFE 64347683:
Insert the clamp into the longitudinal hole in the
edge of the cabinet's frame body and fasten it
with a bolt to the floor. Allowed maximum
distance between the fastening clamps is 800
mm.
Fastening hole distances for the common cabinet
are given in
Fastening clamp hole distances
Fastening bolt: M10 to M12 (3/8” to 1/2”).
Cabinet Width
(mm)
Hole Distance (mm)
200
400 a:
250
600 a:
450
800 a:
650
1000
a: 350, b: 150, a: 350
1500
a: 350, b: 150, a: 350, b: 150, a: 350
Fastening clamp
Fastening clamp hole distances
Dimensions of fastening clamp
Mechanical Installation
3ADW000352R0101 DCS800-A Installation Manual e a