252
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
Group 83: AP control
83.01 AdapProgCmd (AP command)
Selects the operation mode for AP:
0 = Stop
stop, AP is not running and cannot be edited, default
1 = Start
running, AP is running and cannot be edited
2 = Edit
edit, AP is not running and can be edited
3 = SingleCycle
AP runs only once. If a breakpoint is set with BreakPoint (83.06), AP will stop before the
breakpoint. After the SingleCycle AdapProgCmd (83.01) is automatically set back to
Stop.
4 = SingleStep
Runs only one function block. LocationCounter (84.03) shows the function block number,
which will be executed during the next SingleStep. After a SingleStep AdapProgCmd
(83.01) is automatically set back to Stop. LocationCounter (84.03) shows the next
function block to be executed. To reset LocationCounter (84.03) to the first function block
set AdapProgCmd (83.01) to Stop again (even if it is already set to Stop).
A136 NoAPTaskTime [AlarmWord3 (9.08) bit 3] is set when TimeLevSel (83.04) is not set to 5 ms, 20 ms,
100 ms or 500 ms but AdapProgCmd (83.01) is set to Start, SingleCycle or SingleStep
Note:
AdapProgCmd (83.01) = Start, SingleCycle or SingleStep is only valid, if AdapPrgStat (84.01)
≠
Running.
Int. Scaling: 1 == 1
Type: C
Volatile:
N
St
o
p
S
ingl
eS
tep
St
o
p
-
83.02 EditCmd (edit command)
Edit AP. EditCmd (83.02) is automatically set back to Done after the chosen action is finished:
0 = Done
no action or edit of AP completed, default
1 = Push
Shifts the function block in the spot defined by EditBlock (83.03) and all subsequent
function blocks one spot forward. A new function block can be placed in the now empty
spot by programming its parameter set as usual.
Example:
A new function block needs to be placed in between the function block number four
(84.22) to (84.27) and five (84.28) to (84.33). In order to do this:
1. set AdapProgCmd (83.01) = Edit
2. set EditBlock (83.03) = 5 (selects function block 5 as the desired spot for the new
function block)
3. set EditCmd (83.02) = Push (shifts function block 5 and all subsequent function
blocks one spot forward)
4. program empty spot 5 by means of (84.28) to (84.33)
2 = Delete
Deletes the function block in the spot defined by EditBlock (83.03) and shifts all
subsequent function blocks one spot backward. To delete all function blocks set
EditBlock (83.03) = 17.
3 = Protect
Turns all parameters of AP into protected mode (parameters cannot be read or written
to). Before using the Protect command set the pass code by means of PassCode
(83.05).
Attention: Do not forget the pass code!
4 = Unprotect
Reset of protected mode. Before the Unprotect command can be used, PassCode
(83.05) has to be set.
Attention: Use the proper pass code!
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
D
one
U
npr
ot
e
c
t
D
one
-
83.03 EditBlock (edit block)
Defines the function block which is selected by EditCmd (83.02) = Push or Delete. After a Push or Delete
EditBlock (83.03) is automatically set back to 1.
Note:
To delete all function blocks set EditBlock (83.03) = 17.
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
0
17
0
-
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...