ABB D1M 20 User Manual Download Page 37

37

D1M 20 

POWER METER USER MANUAL

NUM

CONF>ALAM>NUM

•  “Add” indicates that the alarm is not yet present. If it 

needs to be added, press the button “

OK

” to go to the 

event and configure the subsequent parameters.

•  “Edit” indicates that the alarm is already present. If it 

needs to be modified, press the button “

OK

” to go to 

the event and modify the configurations.

If certain event needs to be deleted from the alarm list, the alarm variable is selected as “NONE”. For 

details, see “

VARIABLE

”.

VARIABLE

Select one variable as alarm variable or event variable.

CONF>ALAM>VRR

  

Variable

Description

VLN

Phase voltage

VLL

Line voltage

I

Phase current

IN

Neutral current

P

Active power

Q

Reactive power

S

Apparent power

PT

Total active power

QT

Total reactive power

ST

Apparent power

PF

Power factor

PFT

Total power factor

F

Frequency

THDV

Total harmonic distortion of phase voltage

THDI

Total harmonic distortion of current

THDU

Total harmonic distortion of line voltage

None

Nothing

Summary of Contents for D1M 20

Page 1: ...POWER METER D1M 20 User manual D1M 20 User manual 9AKK108468A5638...

Page 2: ......

Page 3: ...3 3 Versions 8 3 4 Overall dimensions 9 3 5 Technical data 9 4 Installation 12 4 1 Assembly 12 4 2 Disassembly 12 4 3 Wiring diagrams 13 5 Access to device 15 5 1 Display 15 5 2 Buttons 17 5 3 Data en...

Page 4: ...EAD 53 8 1 Realtime REAL 54 8 2 Energy ENRG 55 8 3 Power Quality PWQT 57 8 4 Average values AVG 58 8 5 Maximum values MAX 59 8 6 Minimum values MIN 60 8 7 I O 61 8 8 Notifications NOTF 62 8 9 Power Ou...

Page 5: ...exclusively by qualified personnel who have read all of the information relative to the installation Check that the voltage supply and measurement are compatible with the range permitted by the device...

Page 6: ...or damages and or losses related to such security breaches unauthorized access interference intrusion leakage and or theft of data or information D1M products can only work on a Local Area Network it...

Page 7: ...7 D1M 20 POWER METER USER MANUAL 2 Packaging contents Packaging contents 1 Power meter D1M 20 2 Installation manual 3 Calibration certificate 1 2 3...

Page 8: ...t TRMS Current TRMS Voltage Frequency Active Reactive and Apparent Power Power Factor Operating timer countdown timer Energy Active Reactive and Apparent Energy Four quadrant Import Export Net Tariffs...

Page 9: ...61557 12 PMD S K55 0 5 Active energy IEC61557 12 Class 0 5 IEC 62053 22 Class 0 5S Reactive energy IEC61557 12 Class 1 IEC 62053 24 Class 1 Active power IEC 61557 12 Class 0 5 Reactive power IEC 61557...

Page 10: ...channels 2 Voltage 24 VDC Frequency 1kHz Digital Output 2 Number of channels 2 Voltage 24 VAC DC Current 100mA DC Width 10 990ms Mechanical properties Overall Dimensions 89 0mm x 52 5mm x 63 5mm IP de...

Page 11: ...8 1 12 Subnet mask DHCP Manual default 255 255 255 0 Gateway DHCP Manual default 192 168 1 1 Port 502 fixed Standards Power metering and monitoring devices PMD IEC 61557 12 Static meters for AC active...

Page 12: ...12 D1M 20 POWER METER USER MANUAL 12 4 Installation 4 1 Assembly 4 2 Disassembly 1 1 2 2...

Page 13: ...the voltage detection device D1M 20 Modbus D1M 20 Ethernet Type of network D1M 20 can be used on different type of network please refer to chapter 7 Configuration CONF for the configuration on the dev...

Page 14: ...k with 1CT 3 1T PE L1 A L2 B L3 C I1 S1 I2 I3 S2 S1 S2 S1 S2 L1 L2 L3 N Voltage 3P3W1CT Aux PE PE L1 A L2 B L3 C I1 S1 I2 I3 S2 S1 S2 S1 S2 L1 L2 L3 N Voltage 3P3W1CT Aux 2 phase 3 wire network with 2...

Page 15: ...g how to read data and configure related parameters 5 1 Display Front panel D1M 20 products use LCD displayer the front panel of D1M 20 is shown below Operator panel 1 Display area 2 Function buttons...

Page 16: ...ured value or other contents 5 Magnitude Magnitude includes E K and M 6 Icons Indicating various types of state and for further details see the table below Icon description Icon Description Notificati...

Page 17: ...1 OK Confirm the numerical value or option input go to the next level menu Go to the main menu 2 Down Page down numerical value amplifies 10 times Return to the previous level menu 3 Up Page up numer...

Page 18: ...o start setting on the specified parameter page and the parameter starts to blink display The data entry procedure is as follows Short press the Up Arrow button to set the first on the far left numeri...

Page 19: ...Enable the comma Some device configurations allow entering the comma Comma can be displayed by increasing the number with Up after character 9 and before data entry starts again from character 0 Conf...

Page 20: ...ome device configurations allow entering the magnitude k M Once the number has been entered as after step 3 keys Up and Down allow enabling the magnitude K kilo or not Press OK to confirm the magnitud...

Page 21: ...d for the first use PWD A password can be set by the user to protect the Configuration menu and avoid any unwanted modification to the device settings At the first use it is mandatory to define a pass...

Page 22: ...date and time are set no timestamp will be available on the measured data D1M series meter also provides DST Daylight Saving Time RTC CONF UNIT RTC 1 The format of RTC setting page is Year Month Day H...

Page 23: ...e phase two wire and 1 CT 6 4 CT ratio CT D1M is capable to measure current only via indirect connection by means of current transformers CTs 5A or 1A It is needed to set the transformation ratio of t...

Page 24: ...y PRIM and secondary SEC CONF ISTL VT 1 When the number of the primary VT is set press Button OK 2 Use Button Up and Button Down to select the magnitude 3 Press button OK to confirm the setting of the...

Page 25: ...following menus Menu Description UNIT Settings related to the device itself ISTL Settings related to the installation conditions I O Settings related to the pulse LED ALARM Definition of alarm conditi...

Page 26: ...TF Clear the logs of warning error and alarm Reset Avg Max Min Reset and clear the data of Average Maximum and Minimum Reset GLOBAL Complete reset of the device except for the settings and the audit l...

Page 27: ...UNIT RST NTF RESET Avg Max Min Reset and clear the data of Average Maximum and Minimum CONF UNIT RST AVG RESET Global Complete reset of the device except for the settings and the audit log include not...

Page 28: ...INFO includes firmware version product model and peripheral functions etc CONF UNIT INFO Menu Description FW Firmware version contain main board ethernet board D1M20 ETHERNET CRC The CRC value of cur...

Page 29: ...arameter is used to adjust brightness of the display CONF UNIT BRT The default of this parameter is 100 and the adjustable range is 10 100 Energy Saving ENSV In this menu it is possible to define the...

Page 30: ...r time Year month day hour minute second FW Update successful Upgrade counter and firmware version VT Primary setting VT primary value VT Secondary setting VT secondary value CT Primary setting CT pri...

Page 31: ...hase Voltage Line Voltage and Current page It will turn to the home page which was set by users if no activities after inactivity time CONF UNIT HOME PAGE Auto Scroll pages Auto Scroll pages can be se...

Page 32: ...ate the speed of energy consumption It can be configured to output Total Active Import Energy IPEN Total Active Export Energy EPEN Total Reactive Import Energy IQEN Total Reactive Export Energy EQEN T...

Page 33: ...rs for voltage measurement if any Wiring TYPE Set the type of network and number of wires on which the device is installed The three items above must be set during the first startup For details see 6...

Page 34: ...10 100 1000 5000 pulses for each kWh kvarh kVAh or 10 50 100 pulses for each Wh varh VAh Manual setting 1 and 999999 pulses for each MWh Mvarh MVAh The pulse width could be configured once DOs were c...

Page 35: ...ively set a pulse ratio associated to the pulse counter and then a unit of measurement to be associated to the pulses The pulse ratio is set manually between 1 to 999999 Electricity Variable Descripti...

Page 36: ...e delay the alarm will be generated and when the alarm variable recovers to the normal range and exceeds the hysteresis and delay the alarm will be released Alarm can be connected to certain DO to con...

Page 37: ...deleted from the alarm list the alarm variable is selected as NONE For details see VARIABLE VARIABLE Select one variable as alarm variable or event variable CONF ALAM VRR Variable Description VLN Pha...

Page 38: ...e selected CONF ALAM PHSE Phase Description L1 Phase 1 L2 Phase 2 L3 Phase 3 TOT Total phase when PT QT ST PFT is selected variable Different variables contain different phases so the phase selection...

Page 39: ...999MVA Power Factor 0 000 0 999 Current 0 000 50 120 kA Neutral Current 0 000 50 120 kA Phase Voltage 0 000 750 120 kV Line Voltage 0 000 750 3 120 kV Current THD 0 99 9 Phase Voltage THD 0 99 9 Line...

Page 40: ...ms are set by default in log mode which means that alarms are stored in flash memory when the alarm is triggered CONF ALAM LOG PORT Each alarm event can be connected with certain DO and different alar...

Page 41: ...RTC real time clock Tariff RTC set Set the day type special day weekday weekend Set the tariff configurations for different day type Current tariff Read only T1 T4 TARIF menu tree as below TARIF TARIF...

Page 42: ...urce It is possible to select from 4 options include NONE disable COMM communication DI digital input RTC real time clock CONF TARF TARF SOURCE Tariff RTC set If user select tariff source as RTC tarif...

Page 43: ...43 D1M 20 POWER METER USER MANUAL Set Day Type Set Monday Tuesday Wednesday Sunday as weekday or weekend CONF TARF SET RTC SET DAY TYPE...

Page 44: ...Set weekday time Enable or disable T1 and set start time HHMM of T1 same as T2 T3 T4 CONF TARF SET RTC SET WKDY TIME Set weekend time Enable or disable T1 and set start time HHMM of T1 same as T2 T3 T...

Page 45: ...Set Special Day Set the total number of special day 0 50 CONF TARF SET RTC SET SPECDAY TOT After setting the total number of special day add special day SPCE DAY one by one in the format YY MM DD CONF...

Page 46: ...SER MANUAL And then enable or disable special day T1 and set start time HHMM of T1 same as T2 T3 T4 CONF TARF SET RTC SET SPEC TIME Current tariff User could read the tariff NONE T1 T2 T3 T4 used curr...

Page 47: ...iption Modbus RTU ADDR Bus address BAUD Baud rate BYTE Byte format Modbus TCP IP DHCP Enable Disable DHCP function IP IP address MASK Subnet mask GW Default Gateway In the communication process whiche...

Page 48: ...OMM PARITY The optional byte formats include BYTE Description 8E1 8 even parity bits and 1 stop bit 8O1 8 odd parity bits and 1 stop bit 8N1 8 No Parity bits and 1 stop bit Address ADDR For the device...

Page 49: ...et mask assigned by the host will be used CONF COMM DHCP The default state of DHCP is NO i e turned off IP IP comprises 4 segments Each time Button OK is pressed the next segment can be set CONF COMM...

Page 50: ...the devices that have the same subnet mask within the same LAN can communicate with each other CONF COMM MASK The default MASK is 255 255 255 0 GW The default GW is the node address that forwards the...

Page 51: ...this time was set CO2 Equivalence Converse the Active Energy Import Total to CO2 Currency Equivalence Converse the Active Energy Import Total to Currency CONF OTHR Average Time Interval AVG AVG needs...

Page 52: ...The factor between the Active Energy Import Total and CO2 range is 0 001 9 999Kg kWh CONF OTHR EQUI CO2 Currency Equivalence Converse the Active Energy Import Total to Currency The factor between the...

Page 53: ...it includes the following menus Menu Description REAL Real time measurements ENRG Energy measurements PWQT Power quality AVG Average of measurement variable MAX Maximum value of measurement variable...

Page 54: ...I and active power total VLN Phase voltage VLL Line voltage I Current IN Neutral current when WIRI is selected as 3 3T 3 2T 3 1T or 1N1T this data is absent P Per phase active power when WIRI is selec...

Page 55: ...55 D1M 20 POWER METER USER MANUAL 8 2 Energy ENRG READ ENRG...

Page 56: ...d apparent energy SEN Total exported apparent energy T1 PEN Tariff T1 total exported active energy T1 QEN Tariff T1 total exported reactive energy T2 PEN Tariff T2 total exported active energy T2 QEN...

Page 57: ...e when WIRI is selected as 3 3T 3 2T 3 1T this data is absent THDU Total harmonic distortion of line voltage when WIRI is selected as 3 3T 3 2T 3 1T or 1N1T this data is absent THDI Total harmonic dis...

Page 58: ...e Average Time Interval sub menu under 7 7 Other OTHR including the following items READ AVG AVG Description VLN Average phase voltage VLL Average line voltage I Average current IN Average neutral cur...

Page 59: ...ximum line voltage I Maximum current IN Maximum neutral current P Maximum average per phase active power calculated over AVG time Q Maximum average per phase reactive power calculated over AVG time S...

Page 60: ...um line voltage I Minimum current IN Minimum neutral current P Minimum average per phase active power calculated over AVG time Q Minimum average per phase reactive power calculated over AVG time S Min...

Page 61: ...the product version Menu Description DO STATE State of digital output port DO1 PULSE DO1 Pulse counter DO2 PULSE DO2 Pulse counter DI STATE State of digital input port DI1 PULSE DI1 Pulse energy DI2...

Page 62: ...settings ERROR Errors list related to the device and to its self diagnostics Alarms ALAM ALARM is generated based on the Alarm configured by the user When the conditions meet the alarm parameters the...

Page 63: ...rent 1 Missing I2 MISS Current 2 Missing I3 MISS Current 3 Missing I1 REVES Current 1 Reverse I2 REVES Current 2 Reverse I3 REVES Current 3 Reverse I12 REVES Current 1 with 2 Reverse I23 REVES Current...

Page 64: ...sappear until the error is solved ERROR comprises error count and specific error message READ NOTF ERR Error Definition ALOG ERR Audit log error FLSH ERR Flash chip error or RAM memory CRC error FW IN...

Page 65: ...se 2 counters below Error Definition TIMR UP Count the total using time start from first commissioning The maximum time up value is up to 99999999 hours 11415 years and can be reset see Reset RST sub...

Page 66: ...ER USER MANUAL 9 Conclusion Thank you for using ABB D1M 20 series Power Meter and reviewing this user manual In the future if you encounter any problems please contact ABB technical support we will be...

Page 67: ......