INSTALLATION AND WIRING
BDS0029 rev 11
Cylon® FBXi
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
1
BDS0
02
9 r
ev 1
1
Ground
Common
CAUTION - DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED.
REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED BY THE
MANUFACTURER. DISPOSE OF USED BATTERIES ACCORDING TO THE MANUFACTURER'S
INSTRUCTIONS.
Supply Requirements
24 V AC ±20 % 50/60 Hz
Supply
Rating
FBXi
20 VA (no FLX modules)
FBXi + 1 x FLX
32 VA
FBXi + 2 x FLX
44 VA
|
|
FBXi + 16 x FLX 68 VA
FLX Power Connection
Proprietary FLX bus connector
carries power and comms from
FBXi unit. FBXi-X256 can supply
power to up to 4 FLX modules.