ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
21
4.2.2
Mounting CSU-2
This section describes the procedure to mount the CSU-2.
The procedure is divided into the following components:
• CSU-2
• Current Sensors
Placing CSU-2
The CSU-2 can be mounted anywhere in the switchgear,
for example in the breaker cubicle or in a separate control
cabinet.
Mounting CSU-2
This section describes how to mount the CSU-2 at its
location.
The CSU-2 can be mounted on:
• A wall
• DIN Rail
Mounting on wall
Follow the steps below to mount the CSU-2 on the wall:
1.
Predrill holes in the wall to fit screws 5M.
See
for dimensions.
2.
Place the CSU-2 on the wall.
3.
Screw-in each corner of the CSU-2.
4.
Use a torque wrench and torque the screws to
2.4 Nm.
Mounting on a DIN rail
Follow this procedure to mount the CSU-2 on a DIN rail:
1.
Hook the CSU-2 to the DIN rail.
2.
Snap the CSU-2 on to the rail then release the barrier.
Figure 3
Mounting on wall
1SFC170020M0201
2,4 Nm
145
130
M5
Figure 4
Mounting on DIN rail
1SFC170020M0201
3
1
2
35
7,5 / 15
04
Summary of Contents for CSU-2LV
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 12: ......
Page 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Page 18: ......
Page 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Page 30: ......
Page 38: ......
Page 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Page 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Page 70: ......
Page 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Page 76: ......
Page 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...