ABB CPS6000 Quick Start Manual Download Page 3

 

Page 3

 

 

 

© 2023 ABB. All rights reserved.

 

CPS6000_Series II External Distribution_QSG

 

Version 2.0

 

 

 

The  figure  (right)  shows  the  DC  circuit  description  for  the 

distribution system. The system is equipped with 20 

(19” 

panel) or 

26  (23” 

panel)  bullet

-

style  distribution  positions.  Each  of  the 

positions  in  the  distribution  panel  are  selectable  between  either 

battery inputs or load outputs. 

 

Breaker sizes up to 250A, TPS fuses to 70A and GMT fuses to 12A are 
available.  DC Connections are made with double hole lugs on ¼

-

20 

studs  on 

5/8” 

centers.  The  maximum  tongue  width  for  breaker 

connections is 

0.68”. 

 

Load  and  battery  cabling,  showing  multi

-

pole  adapters 

installed in distribution space

 

The  correct  multi

-

pole  adapters  must  be  used  with  multi

-

pole breakers

 

Step # 3 –

 

Connect DC Output to Loads and Batteries

 

Ordering code

 

Description

 

Picture

 

850021775

 

-

 pole Adapter bus for 100

-

150A breakers; used for 

3/8” 

on 

1” 

lugs (order 2 per 3pole breaker to 

accommodate load and return lugs.)

 

 

850021955

 

-

 pole Adapter bus for 200

-

250A breakers; Centered connection (order 2 per 3 pole breaker to 

accommodate load and return lugs.)

 

 

Summary of Contents for CPS6000

Page 1: ...sockets Heat shrink gun Screw Drivers 1 and 2 Phillips Torque wrench 0 240 in lb 28 Nm Cable crimpers Information Tools Required For systems with rear access AC terminal box The shelf is installed wit...

Page 2: ...AC Input cords Each Rectifier shelf comes equipped with rear access terminal blocks and conduit fittings for ac connection The AC feeds may be either 110 VAC or 208 220VAC depending on the rectifier t...

Page 3: ...able DC Connections are made with double hole lugs on 20 studs on 5 8 centers The maximum tongue width for breaker connections is 0 68 Load and battery cabling showing multi pole adapters installed in...

Page 4: ...Connect LAN Office Alarm Alarm Inputs and Thermal Probes to J5 J4 J3 and J2 respectively as shown right Special Cables are available for these purposes if required Step 6 Initial Start Up Verify that...

Page 5: ...o reflect the system alarm status as follows Green Normal Amber Minor Alarms Present Red Major Alarms Active The up and down arrow keys can be used to adjust screen contrast when the controller is dis...

Page 6: ...ctor J4 provides access to the primary customer alarm output interface Connector J4 is a 20 pin right angle header with latching capability Standard color coded cable assemblies are available Office A...

Page 7: ...ts reserved CPS6000_Series II External Distribution_QSG Version 2 0 Version Date Description of the change 1 0 07 2012 Initial release 2 0 07 11 2023 Updated as per ABB template Change History exclude...

Page 8: ...ail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustr...

Reviews: