Operation
ABB, 1SBC159102M0202
19
Start CP400Soft and open the application file to be downloaded. Make sure that
the communication parameters are correctly configured. Also remember to
compile the file before downloading it. The file has to be compiled every time a
change has been made in the file before downloading it.
Then select
Application/Download Firmware and Application
in CP400Soft if
it is a first time to download the application to the operator terminal; otherwise,
select
Application/Download Application
. The following appears on the screen
while the operator terminal is downloading:
6.7 Uploading an Application
An application can also be uploaded from the operator terminal to the PC.
Thus, a user can save an application as a *.V6F file in CP400Soft for future use.
Make sure that the operator terminal and the PC are connected according to
section
6.6 Downloading an Application
. Set the dip switch
SW7 = ON
. After
the self-test, the system menu will be displayed on the screen and the operator
terminal is ready to upload the application.
Warning:
To avoid an electrical shock, be sure to switch off the power before connecting the
communication cable to the operator terminal.