ABB CP Series Instruction Leaflet Download Page 7

Type CP Reverse Phase Relay

41-222.2J

7

A. CP UNIT

1. Contacts

 - Apply sufficient voltage to the relay,

to make the disc float in the center of its travel.
Move either of the adjustable contacts until it just
makes with the moving contact. If, the two con-
tacts pointers do not meet at the same point on
the scale, adjust the follow on both adjustable
contacts. The contacts should just make with the
moving contacts when the pointers meet on the
scale. Approximately the same follow should be
in each of the adjustable stationary contacts.

2. Minimum 

Trip 

Voltage

 - The adjustment of the

spring tension in setting the minimum trip voltage
is most conveniently made with the damping
magnet removed.

Set either of the adjustable stationary contacts in the
center of its travel. (For example, on the 120 volt
relay, set the contact on the 95 volt setting.) Apply
this voltage to the relay. Wind up the spiral spring by
means of the spring adjuster until the stationary
contact and moving contact just make.

Check the other scale markings by setting the adjust-
able contact on these markings and applying the cor-
responding voltage. The moving contact should
make and break within plus or minus 3% of the value
marked on the scale.

3.

Time Curve Calibration

 - Install the permanent

magnet and connect the relay as per the circuit
of Fig. 8.

Set the high voltage contact on 100 volts and the low
voltage contact on 70 volts. (For the 240 volt relay,
multiply these values by two. Similarly for the 480
volt relay, multiply these values by four.) For the 208
volt relay set the high voltage contact on 170 volts
and the low voltage contact on 120 volts. Apply rated
voltage and frequency to the relay to allow the high
voltage contact to make. Suddenly drop the voltage
to zero and adjust the permanent magnet gap until
the relay operates in 3.7 ± .15 sec.

Check the closing time of the high voltage contact by
use of Fig. 9. With the voltage originally zero, sud-
denly apply rated voltage and frequency to the relay.
The high voltage contact should close in 3.9 seconds
± 0.2 sec.

B. INDICATING CONTACTOR SWITCH (ICS)

Close the main relay contacts and pass sufficient d-c
current through the trip circuit to close the contacts of
the ICS. This value of current should not be greater
than the particular ICS setting being used. The indi-
cator target should drop freely.

7.0

RENEWAL PARTS

Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to the customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.

8.0

ENERGY REQUIREMENTS

The type CP relay when energized at rated fre-
quency and voltage balanced 3 phase has the follow-
ing VA burden for each phase.

The continuous voltage rating of the relays is 110%
of rated voltage.

Freq.

Hertz

Phase

Watts

Vars

VA

Lagging
Power
Factor
Angle

60 

Phase A
Phase B 
Phase C

.25
.37 

1.11

2.82
1.92
2.50

2.83
1.96
2.73 

85
79
66

50

Phase A
Phase B
Phase C

.35
.53

1.48

3.37
2.28
2.79

3.39
2.34
3.16

84
77
62

Summary of Contents for CP Series

Page 1: ......

Page 2: ...41 222 2J Type CP Reverse Phase Relay 2 Sub 5 184A202 Fig 2 Internal Schematic of the Type CP Relay with Independent Contacts in the Type FT 11 Case Fig 1 Type CP Relay Without Case ...

Page 3: ...able high and low voltage contacts which can be set around the periph ery of a scale The ranges of adjustment of the con tacts are as follows 120 volt relay 70 to 120 volts 240 volt relay 140 to 240 volts 480 volt relay 280 to 480 volts 208 volt relay 120 to 220 volts If either of the adjustable contacts are set for a value of voltage within these ranges the relay will just close its contacts when...

Page 4: ... connections may be made directly to the terminals by means of screws for steel panel mounting or to the terminal stud furnished with the relay for thick panel mounting The terminal stud may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench For detail information on the FT case refer to Instruc tion Leaflet 41 076 5 0 SETTINGS There are two...

Page 5: ...ts to insure correct operation of this relay have been made at the factory Upon receipt of the relay no adjustments other than those covered under Settings should be required ACCEPTANCE CHECK The following check is recommended to insure that the relay is in proper working order A CP UNIT 1 Contacts Set the left hand adjustable contact in the center of the scale and adjust the voltage until the mov...

Page 6: ...drop freely 6 1 ROUTINE MAINTENANCE All relays should be inspected periodically and the time of operation should be checked at least once every year or at such other time intervals as may be dictated by experience to be suitable to the particular application All contacts should be periodically cleaned A contact burnishes S 182A836HO1 is recommended for this purpose The use of abrasive material for...

Page 7: ...For the 240 volt relay multiply these values by two Similarly for the 480 volt relay multiply these values by four For the 208 volt relay set the high voltage contact on 170 volts and the low voltage contact on 120 volts Apply rated voltage and frequency to the relay to allow the high voltage contact to make Suddenly drop the voltage to zero and adjust the permanent magnet gap until the relay oper...

Page 8: ...ve Phase 3 Phase 3 or 4 Wire S P D T with ac Independent Voltage Switch in Type FT 11 Case Fig 11 Relay Type CP Reserve Phase 3 Phase 3 or 4 Wire S P D T Contacts with Indicating ac Contactor Switch in Low Voltage Circuit in Type FT 11 Case Sub 1 184A469 Sub 1 184A836 ...

Page 9: ...Type CP Reverse Phase Relay 41 222 2J 9 Fig 12 External Schematic Diagram of the Type CP Relay in the Type FT 11 Case Sub 1 184A200 ...

Page 10: ... 222 2J Type CP Reverse Phase Relay 10 Fig 13 Relay Type CP Reverse Phase 3 Phase 3 or 4 S P D T with A C S in Low Voltage Circuit and with A C Independent Voltage Switch in Type FT 11 Case Sub 3 879A900 ...

Page 11: ......

Page 12: ...ABB Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 Telephone 1 954 752 6700 Fax 1 954 345 5329 www abb com substation automation IL 41 222 2 Revision J ABB ...

Reviews: