13
8
COMMUNICATION…
8.6.1 General Parameters…
Parameter
Mnemonic
Command
Reply Interpretation
Read
(R)
Write
(W)
Control Page Parameters
Time Units
TU
Yes
Yes
0 = Seconds
1 = Minutes
Cycle Time
CT
Yes
Yes
1.0 to 300.0 seconds (0.9 = ON/OFF)
Hysteresis Value
HY
Yes
Yes
0.0 to 5.0(%)
Proportional Band
PB
Yes
Yes
0.1 to 999.9
Integral Action Time
IT
Yes
Yes
1 to 7200 seconds, 7201 = OFF
Derivative Action Time
DT
Yes
Yes
1 to 999.9 seconds, 0 = OFF
Approach Band
AB
Yes
Yes
0.1 to 3.0
P.I.D. Offset
OF
Yes
Yes
0 = 0.0
1 = 50.0
Set Point Parameters
Local Set Point Adjust
Enable
SE
Yes
Yes
0 = No
1 = Yes
Local Set Point High
Limit
SH
Yes
Yes
Any value within the programmed display range
Local Set Point Low
Limit
SL
Yes
Yes
Any value within the programmed display range
Local Set Point
LP
Yes
Yes
Any value within the programmed display range
Set Point Tracking
Enable
TE
Yes
Yes
0 = No
1 = Yes
Set Point Type Select
State
TS
Yes
Yes
0 = No
1 = Yes
Second Set Point State
UE
Yes
Yes
0 = None
1 = Dual
2 = Remote
Dual Set Point High
Limit
UH
Yes
Yes
Any value within the programmed display range
Dual Set Point Low
Limit
UL
Yes
Yes
Any value within the programmed display range
Remote Set Point High
Limit
MH
Yes
Yes
Any value within the programmed display range
Remote Set Point Low
Limit
ML
Yes
Yes
Any value within the programmed display range
Ratio Adjust Enable
(Remote Set Point)
RE
Yes
Yes
0 = No
1 = Yes
Ratio Adjust Value
(Remote Set Point)
RO
Yes
Yes
0.010 to 9.999
Bias Adjust Enable
(Remote Set Point)
BE
Yes
Yes
0 = No
1 = Yes
Bias Adjust Value
(Remote Set point)
BO
Yes
Yes
–100 to +100
Select Set Point Type
TY
Yes
Yes
0 = Local
1 = Balance
2 = Second