![ABB COM600 series User Configuration Manual Download Page 61](http://html1.mh-extra.com/html/abb/com600-series/com600-series_user-configuration-manual_3390418061.webp)
Automatic execution
6.2.
In the automatic execution mode, the sequence execution simply runs through each step
without any need of manual intervention.
To run the sequence in automatic mode:
1.
Make sure that the execution mode button indicates Auto. If not, double-click the
button and select Auto.
2.
Double-click Start/Stop and in the following dialog, click Start to begin the
sequence execution.
If needed, stop the sequence execution in the same dialog by selecting Stop. As
each step is executed, the corresponding breaker/switch mapped for the step is
controlled to the desired state.
An example of a four-step sequence in automatic execution mode is shown in Figure 6.2-
1.
automatic_execution.png
Figure 6.2-1 A four-step sequence in automatic execution mode
Manual execution
6.3.
In the manual execution mode, the execution pauses and waits for user acknowledgement
after each step in the sequence.
To run the sequence in manual mode:
1.
Make sure that the execution mode button indicates Manual. If not, double-click
the button and in the following dialog, select Manual.