![background image](http://html1.mh-extra.com/html/abb/com600-series/com600-series_owners-operators-manual_3389455030.webp)
HMI_Data_Historian_menu.bmp
Figure 3.9-1 Data Historian menu item shown in Web HMI
For more information about configuring the data historian, see section Configuring Data
historian in COM600 User's Manual. For information about the actual usage of data
historian information, see COM600 Data Historian Operator's Manual.
Disturbance data upload
3.10.
Disturbance recordings
3.10.1.
Most of the IEDs are equipped with a Disturbance recording function that locally stores
the values of currents, voltages, frequencies, and binary signals in a disturbance file
before, during, and after a protection event. These disturbance files are copied to the
COM600 computer automatically, if the function has been configured in SAB600.
You can see the list of disturbance recordings by clicking on Disturbances below the
desired IED in the substation structure.