Description
Value or Value range/ Default
Property/ Para-
meter
Defines whether a new indication value
overwrites an older one in the queue.
1 = True
0 = False
Default: 0 = False
Over Write
Priority of ASDU. This property defines
how the ASDU sent is placed in the class
1 and class 2 queues.
0...3
End of queue = 0
Middle = 1, 2
Beginning of queue = 3
Priority
Maximum update rate of indication
changes between OPC server and client
in milliseconds. 0 means that server sends
all the changes to the client.
0...60000
Default: 0
Update Rate
Data Class Spe-
cific
Specifies if a value of indication signal is
sent as inverse value.
True = 1
False = 0
Default: False
Send as Inverse
Value
Specifies if a value of indication signal is
sent as single point value.
True = 1
False = 0
Default: False
Send as Single
Point
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2
Default: Send Long Format
Time Tag
Time Tag Handling
Integer status (INS)
3.4.5.4.
Information in the following table applies also to the Internal INS data object.
Table 3.4.5.4-1 Configurable INS properties for OPC client
Description
Value or Value range/ Default
Property/ Para-
meter
Basic
34
1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual