Description
Value or Value range/ Default
Property/ Para-
meter
Data Class Spe-
cific
Specifies if a value of indication signal is
sent as double point value.
True = 1
False= 0
Default: False
Send as Double
Point
Specifies if a value of indication signal is
sent as inverse value.
True = 1
False = 0
Default: False
Send as Inverse
Value
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2
Default: Send Long Format
Time Tag
Time Tag Handling
Double point status (DPS)
3.4.5.3.
Table 3.4.5.3-1 Configurable DPS properties for OPC client
Description
Value or Value range/ Default
Property/ Para-
meter
Basic
Common data class according to IEC
61850.
DPS
Common Data
Class
Addresses
IEC address for indication.
0...16777215
Default: 0
Indication Address
Common
Class of ASDU. Data sent from the slave
to the master can be assigned to two
classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
class 2.
1 = Class 1
2 = Class 2
Default: 1 = Class 1
Class
Interrogation group. 1 - 16 general or 1 -
4 counter interrogation.
1...16 (general) or 1...4 (coun-
ters)
Interrogation Group
33
Station Automation COM600 3.4
1MRS755382
IEC 60870-5-101 Slave (OPC) User's Manual