CMS-660 SYSTEM
CIRCUIT MONITORING SYSTEM (CMS)
15
—
Installation Guide
—
Flat Cable – Assembly of Connectors
Mark the desired placement of the connector with a pen:
1. Press the flat cable into the cable duct of the
connector housing.
2. Insert the connector into the connector
housing at the marked position.
3. Press together using parallel pliers.
Repeat the process at all other marks.
• Use the connectors only once
• Connect max. 32 sensors to the CMS-Bus interface of the control unit
• Consider the maximum flat cable length
• Flat cable should not exert force on the sensor, otherwise measuring deviations may occur
• Keep a distance of 5.5mm minimum between the flat cable and uninsulated live parts
CMS
BUS
DIGITAL
INPUT
—
Position of the Cable
The cable must not bend directly above the
sensor. If you use open-core sensors, make sure
the cable is at the correct position, otherwise
measuring deviations may occur.